MSC-CB-AC-FI8FO4S
Checklist after installation
With the MSC system, faults can be detected in the individual modules. To ensure trouble-free operation of the system, the
following checks are to be performed during setup and at least once a year:
1. Fully check the system (see section "Checking the system" in the manual on the supplied CD-ROM).
2. Check whether all cables are inserted correctly and the terminal blocks are tightened properly.
3. Check whether all LEDs (indicators) light up correctly.
4. Check whether all sensors connected to the MSC system are positioned correctly.
5. Check whether the MSC system is properly fastened to the DIN rail.
6. Check whether all external indicators (lamps) function correctly.
Technical data
Module
PFH
(IEC 61508:2010)
D
Operating voltage
Power dissipation
Digital INPUTS (no./description)
INPUT_FBK/RESTART (no./description)
Test OUTPUT (no./description)
Digital OUTPUTS (no./description)
OSSD (no./description)
Slot for memory card M-A1
Connection to PC
Connection to extension modules
Dimensions (H x W x D)
WARNING
Ì
To ensure trouble-free operation of the module MSC-CB, it is essential to observe all regulations,
instructions and warnings in the MSC manual on the "EUCHNER Safety Designer" CD.
Ì
EUCHNER rejects any and all liability for incidents resulting from partial or full non-compliance with
the aforementioned notes.
10
(translation of the original operating instructions – brief operating instructions) 2541031-01-10/20
MSC-CB-AC-FI8FO4S
1.34 E-08
24 VDC ± 20%
3 W max.
8/ PNP active high as per EN 61131-2
Up to 4/external device monitoring (EDM)/
Automatic or manual mode via START button possible
4/ for checking for short circuits, overload states
Up to 4/programmable – PNP active high
4 single-channel/safe safety outputs – PNP active high 400 mA at 24 VDC max.
USB 2.0 (Hi Speed) – cable length max. 3 m
Via proprietary MSCB 5-way bus from EUCHNER
108 x 22.5 x 114.5 mm
Fitted