9.3.2
Testing
Procedure, test
Safety circuit integration
Internal: Protection area is free
Internal: Select other floor (travel
command / reset)
Internal: Interrupt light curtain
during journey
Internal call signal wiring
Internal: Enable light curtain
External: Call elevator with external
call
Internal: Select other floor (travel
command)
Latch_Out (Riegel_out) wiring
Internal: Light curtain interrupted
Internal: Select other floor (travel
command
Internal: Enable light grid repeat
travel command
Step test
Internal: Attempt to induce an
emergency stop shortly before the
zone so that the elevator slips within
the zone (see Chapter 5.2.7)
Internal: Select the same floor again
while the light curtain is enabled.
(travel command / reset) and wait
briefly.

10. Display and operating elements

10.1 Tumbler switch on control unit plug-in

A tumbler switch is located on the front of the control unit
plug-in which has a central position, a contact function to
the left and a switch function to the right.
10.1.1 Normal operating mode
The tumbler switch is at "0" (central position).
10.1.2 Operation with buzzer
The buzzer is switched on in the "Loudspeaker" position (to
the right). This operating mode is used for an audible check
during the installation.
10.1.3 Test
A calibrating procedure is conducted when the button on
"T" is actuated (to the left). The LED's "Alarm T" and / or
"Alarm R" illuminate simultaneously for the duration of the
calibration. The monitored area should be empty during
this time period. The relay will not enable if the control unit
plug-in detects covered elements, defective transmitters or
defective receivers.
20
Correct reaction
The elevator must stop immediately
if the light curtain is penetrated.
The elevator should not continue
the journey. It should remain
stationary.
The elevator should start moving
and stop at the selected floor.
The
elevator
should
stationary. It should not move.
The door should be locked.
The elevator should start moving
and stop at the selected floor.
It should be impossible to open the
landing door.
It should only be possible to open
the landing door if the cabin is flush
with it. No step should be visible!
10.2 Tumbler switch on plug-in system
A tumbler switch is located on the front of the plug-in
system controller. Actuating this "service button" has
the same function as an internal call signal. The elevator
technician can close the safety circuit again from the
plug-in system controller in the event of an emergency
stop during commissioning and inspection control during
installation.
10.3 "Status" output on control unit plug-in
The 'Status' output continuously indicates the status of
the light curtain and can be used to control an automatic
landing door or for load control. The switch relay (CEDES
Part No.: 100 098) is available as an accessory for this
purpose.
Measures in event of wrong reaction
Loop safety circuit 1 into the elevator
safety sequence.
Check that the override signal sequence
is correct (see Chapter 5).
An external call signal should not be
carried out on the system control rack.
Deactivate external call signal with
contact (K30/K31) if necessary.
Check internal call signal wiring (no
level?)
remain
Loop in Latch_Out (Riegel_Out) (see
Chapter 4.2.7).
Check overall integration of system and
elevator signals.
Plug in latch stopping time jumper at
10 min.
The latch stopping time should only
be set at 2.5 or 10 s for elevators with
recall!
controller (Service button)
(Loading or door control)
English
© CEDES | V 2.8