9-6. In Case Refrigerant is Leaking

CAUTION
(1) Detecting Leaks
Use the detector for R410A to locate refrigerant leak
points.
(2) Recovering refrigerant
Never release the gas to the atmosphere; recover
residual refrigerant using the refrigerant recovery unit for
R410A, instead.
Do not reuse the recovered refrigerant because its
composition will have been altered.
(3) Welding leaking points
Confirm again that no residual refrigerant exists in the unit
before starting welding.
Weld securely using flux and wax for R410A.
Prevent oxide film from forming inside the tubes utilizing
substitution with nitrogen (N2) in the refrigerant circuit of
the unit. Leave ends of tubes open during welding.
(4) Checking for sealing
Use nitrogen gas for the pressurized gas, and never use
a refrigerant other than R410A. Also do not use oxygen or
any flammable gas.
(5) Evacuation
Use a solenoid valve-installed vacuum pump so that
even if power is cut off in the middle of evacuation of air
due to a power interruption, the valve will prevent the
pump oil from flowing back.
The equipment may be damaged if moisture remains in
the tubing, thus carry out the evacuation thoroughly.
When using a vacuum pump with exhaust air volume
more than 25L/min. and ultimate vacuum pressure rate of
0.05Torr.
Standard time for evacuation
Length of tubing
Evacuation time
(6) Recharging
Recharge unit in the same manner explained on the
previous page "(5) Recharging."
Downloaded from
www.Manualslib.com
Never attempt to charge additional refrigerant when refrigerant has been leaking
from the unit. Follow the procedure described below to locate points of leaks and
carry out repairs, then recharge the refrigerant.
Less than 10 meters
More than 10 minutes
manuals search engine
(1) Detect leaks
(2) Recover refrigerant
(3) Weld leaking points
(4) Check for sealing
(5) Evacuation
(6) Recharge
More than 10 meters
More than 15 minutes
39
OK
OK
OK
OK
OK