ADDRESS SETUP

In this air conditioner, it is necessary to set up the indoor address before starting the operation.
Set up the address in the following procedure.
1. Set up address after wiring work.
2. Be sure to turn on the power in order of indoor unit → outdoor unit. If turning on the power in the reverse
order, a check code [E19] (Error of No. of header units) is output. When a check code is output, turn on the
power again.
3. It requires maximum 10 minutes (Usually, approx. 5 minutes) to set up automatically an address to 1 line.
4. To set up an address automatically, the setup at outdoor side is necessary.
(Address setup cannot be performed by power-ON only.)
5. To set up an address, it is unnecessary to operate the air conditioner.
6. Manual address setup is also available besides automatic setup.
Automatic address : Setup from SW15 on the interface P.C. board of the header unit
Manual address
* It is temporarily necessary to set the indoor unit and wired to 1 : 1.
(In group operation and in time without remote controller)
Automatic Address Setup
Without central control : To the address setup procedure 1
With central control
(Example)
Address setup procedure
Wire systematic diagram
Address setup procedure 1

Turn on power of indoor/outdoor units.
(In order of indoor → → → → → Outdoor)
After approx. 1 minute, check that U. 1. L08 (U. 1. flash) is
displayed in 7-segment display section on the interface P.C.
board of the header unit.
ƒ
Push SW15 and start setup the automatic address.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
When the count Auto 1 → Auto 2 → Auto 3 is displayed in
7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to
U. 1. - - - (U. 1. light) , the setup finished.
When perform a central control, connect a relay connector
between [U1U2] of the header unit and [U3U4] terminals.
Downloaded from
www.Manualslib.com
: Setup from the weird remote controller
: To the address setup procedure 2
(However, go to the procedure 1 when the central control is performed in a single refrigerant line.)
In case of central control in a single refrigerant line
To procedure 1
Outdoor
Central remote
controller
Indoor
Indoor
Remote
Remote
controller
controller
manuals search engine
CAUTION
In case of central control over refrigerant lines
Outdoor
Outdoor
Central remote
controller
Indoor
Indoor
Indoor
Remote
Remote
controller
controller
12
To procedure 2
Outdoor
Central remote
controller
Indoor
Indoor
Indoor
Remote
Remote
controller
controller
Header unit interface P.C. board
3
SW04
SW05 SW15
2 4
D600 D601 D602 D603 D604
SW01
SW02 SW03
1
1
1
5
U1 U2
U3 U4
For internal
For wiring of
For internal
wiring between
central control
wiring between
indoor and
system
outdoor units
outdoor
U5 U6