Toshiba MMY-MAP0501T8 Installations-Handbuch Seite 17

Aussengeraet
Vorschau ausblenden Andere Handbücher für MMY-MAP0501T8:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

No.
Piping parts
Branching
section
Follower
unit 3
1
Outdoor unit
connecting
piping
Downloaded from
www.Manualslib.com
Name
Y-shape branching joint
6) Selection of branching section
Branching header
T-shape branching joint
Y-shape branching joint
Branching header ∗2
T-shape branching joint
(For link of outdoor units)
∗1: If exceeding the main pipe size, decide the size same to main pipe size.
∗2: Up to total 6.0 of Max. capacity codes is connectable to one line after branching of header.
Follower
Follower
unit 2
unit 1
Header unit
Outdoor
unit
7
Balance pipe
6
6
6
T-shape
branching joint
1
1
1
6
6
2
2
3
Main connecting
piping between
Main piping
outdoor units
manuals search engine
Selection of pipe size
Total capacity code of indoor units
Equivalent to capacity
Below 18.0
18.0 to below 40.0
*1
40.0 to below 70.5
Above 70.5
Below 40.0
For 4
branches
40.0 to below 70.5
Below 40.0
For 8
branches
40.0 to below 70.5
The following 3 types of T-shape branching joint pipes are made to one set.
Arrange the required quantities and combine at the local site.
• Balance pipe
(Corresponding dia. Ø9.5) × 1
• Pipe at liquid side (Ø9.5 to Ø22.1) × 1
• Pipe at gas side
(Ø15.9 to Ø41.3) × 1
4
Branching pipe
Indoor unit connecting pipe
5
6
Y-shape
branching
6
6
joint
4
4
1st branching
5
section
Indoor unit
connecting pipe
14
Model name
Equivalent to HP
Below 6.4
RBM-BY53E
6.4 to below 14.2
RBM-BY103E
14.2 to below 25.2
RBM-BY203E
Above 25.2
RBM-BY303E
Below 14.2
RBM-HY1043E
14.2 to below 25.2
RBM-HY2043E
Below 14.2
RBM-HY1083E
14.2 to below 25.2
RBM-HY2083E
RBM-BT13E
6
Branching header
6
4
5
5
5
Indoor unit
6
4
6
4
5
5
5
Indoor unit
5
5