Herunterladen Inhalt Inhalt Diese Seite drucken

Toshiba MMY-MAP0501T8 Installations-Handbuch Seite 69

Aussengeraet
Vorschau ausblenden Andere Handbücher für MMY-MAP0501T8:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6
ELECTRIC WIRING
Design of control wiring
1. All control wiring is 2-core and non-polarity wire.
2. Be sure to use shield wire for the following wiring to prevent noise trouble.
• Outdoor-outdoor / indoor-indoor / outdoor-indoor control wiring, Central control wiring.
Central control
device
U1
U2
U3
U4
Outdoor unit
Indoor unit
Table-1 Control wiring between indoor and outdoor units (L1, L2, L3),
Note (*1) : Total of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4 )
Table-2 Control wiring between outdoor units (L5)
Table-3 Remote controller wiring (L6, L7)
Downloaded from
www.Manualslib.com
Header
Header
unit
unit
U3 U4
U3 U4
U1 U2
U5 U6
U1 U2 U5 U6
L1
U1 U2
U1 U2
U1 U2
A B
A B
Table-3
Remote
Remote controller
controller
Central control wiring (L4)
Wiring
2-core, non-polarity
Type
Shield wire
Size
1.25 mm² : Up to 1000 m
Length
2.0 mm² : Up to 2000 m (*1)
Wiring
2-core, non-polarity
Type
Shield wire
Size
1.25 mm² to 2.0 mm²
Length
Up to 100 m (L5)
Wire
2-core
Size
0.5 mm² to 2.0 mm²
Length
• Up to 500 m ( L6 + L7 )
• Up 400m in case of wireless remote controller in group control.
• Up to 200m total length of control wiring between indoor units ( L6 )
manuals search engine
Super modular multi system
Table-1
L4
Follower
Follower
Follower
unit
unit
unit
U3 U4
U3 U4
U3 U4
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
L5
L2
U1 U2
U1 U2
A B
A B
A B
5
Header
Follower
unit
unit
U3 U4
U3 U4
U1 U2 U5 U6
U1 U2 U5 U6
Table-1
Table-2
L3
U1 U2
U1 U2
U1 U2
A B
A B
A B
L7
L6
Remote controller

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Inhaltsverzeichnis