Herunterladen Inhalt Inhalt Diese Seite drucken

Selection Of Installation Place; Installation Space - Toshiba MMY-MAP0501T8 Installations-Handbuch

Aussengeraet
Vorschau ausblenden Andere Handbücher für MMY-MAP0501T8:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

2

SELECTION OF INSTALLATION PLACE

Install the air conditioner certainly at a place bearable to weight.
If strength is insufficient, the unit may fall down resulting in human injury.
Do not install the air conditioner at a place where combustible gas may leak.
If gas leaks and is collected at surrounding the unit, the production of fire may be caused.
Upon customer's approval, install the air conditioner at a place where satisfies the following
conditions.
• Place where it can be installed horizontally.
• Place which can reserve a sufficient service space for safe maintenance or check.
• Place where there is no problem even if the drained water flows.
Apply electric insulation between metal section of the building and metal section of the air
conditioner in conformance with the Local Regulation.
Avoid the following places.
• Salty place (seaside area) or place with much gas sulfide (hot spring area)
(If selecting such a place, a special maintenance is required.)
• Place where oil (including machine oil), steam, oil smoke or corrosive gas generates.
• Place where a device generating high frequency (inverter, non-utility generator, medical apparatus, or
communication equipment) is set. (A bad influence may generate by malfunction of the air conditioner, control
error, or noise for such equipment.)
• Place where discharged air of the outdoor unit blows against windows of neighbor.
• Place where operation sound of the outdoor unit transmits.
(Especially at the boundary line with neighbor, install the air conditioner considering the noise.)
• Place unbearable to weight of the unit.
• Place with ill ventilation.

Installation space

Considering functions, reserve space necessary for installation work and servicing.
Air inlet
Air inlet
Installation work/
servicing surface
Square hole for handling
Downloaded from
www.Manualslib.com
Air outlet
Air inlet
Air inlet
NOTES)
∗1 : If there is an obstacle at the upper side of the outdoor unit, reserve
∗2 : Arrange the height of obstacle around two outdoor units up to
manuals search engine
WARNING
CAUTION
(Rear side)
500mm or more
10mm
or more
500mm or more
20mm or more
(Front side)
(A case of 3 units are installed.)
a space by 2000mm or more to the top end of the outdoor unit.
below 800mm from the bottom end of the outdoor unit.
4
Outdoor unit top view
20mm or more
10mm
or more

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Inhaltsverzeichnis