7
P-band for room controller
8
I-time (s) for room controller
9
With a lower temperature on the analogue
Change-over input, the cooling function is
selected
10
With a higher temperature on the analogue
Change-over input, the heating function is
selected
11
Control states: 0=Heat, 1=Heat/Heat,
2=Heat or cooling via Change-over,
3=Heat/Cooling , 4=Heat/Cooling with VAV-
control and forced supply air, 5=Heat/Cool-
ing with VAV-control, 6=Cooling , 7=Cool-
ing/Cooling
12
Time in Bypass mode
13
Disconnect timer with occupancy/unoc-
cupancy
14
Switch on delay for occupancy
15
State connected sensor on AI1:
0=Internal sensor, 1=External room sensor
16
State connected sensor on UI1:
0=None, 1=Change-over digital, 2=Change-
over analogue
18
State connected sensor on DI2:
1=Window contact, 2=Condensation detec-
tor
20
State function of signal on UO1:
0=None, 1=Thermal actuator heat, 2=None,
3=Heating actuator 0...10V, 4=None
21
State function of signal on UO2:
0=None, 1=None, 2=Thermal actuator cool-
ing, 3=None, 4=Cooling actuator 0...10V
29
State output signal range for heating actuator:
0=0...10V, 1=2...10V, 2=10...2V, 3=10...0V
30
State output signal range for cooling actuator:
0=0...10V, 1=2...10V, 2=10...2V, 3=10...0V
31
Period time for heating actuator with thermal
actuator
32
Period time for cooling actuator with thermal
actuator
33-35
No function for this model
36
Time in hours between exercise of heating
actuator
10°C
37
Time in hours between exercise of cooling
actuator
300 s
42
Select if setpoint or actual value is to be
18
shown on display, 0=Actual, 1=Heating set-
point, 2=Cooling setpoint, 3=Average value
of heating and cooling setpoint, 4=Only
22
setpoint adjustment
43
Highest permitted setpoint offset upwards
44
Highest permitted setpoint offset downwards
3
45
Preset operating mode:
1=Unoccupied, 2=Stand-by,
3=Occupied. Forced ventilation is not set in
Occupied mode
46
State operating mode by depressing
120 min
Occupancy button for 5 sec:
0=Off, 1=Unoccupied. Forced ventilation is
10 min
not set in Occupied mode.
47
No function for this model
0 min
48
Min. flow at cooling output with regulating
0
state heat/cool when VAV-control is selected
49
Max. flow at cooling output with regulating
2
state heat/cool when VAV-control is selected
and heating is applied
50
Configuration of fan control:
2
0=No control, 1=The fan is controlled by
heating requirement, 2=The fan is control-
led by cooling requirement, 3=The fan is
3
controlled by heating and cooling
requirement
51
Start signal in % for fan speed 1 on heating
4
or cooling control
52
Start signal in % for fan speed 2
53
Start signal in % for fan speed 3
0
54
Hysteresis for start/stop of fans
0
55
State number of speeds for fan
56
Temperature compensation on AI1
60 s
57
Temperature compensation on UI1
58
Temperature compensation for internal
60 s
room sensor
59
Filter factor for analogue temperature inputs 0,2
60
State NO/NC digital input 1: 0=NO
23
(Normally open), 1=NC (Normally closed)
23
0
3°C
3°C
3
1
20
0
3
20
60
100
5
3
0°C
0°C
0°C
0
RC-DFO
61
State NO/NC digital input 2: 0=NO
(Normally open), 1=NC (Normally closed)
62
State NO/NC universal input 1: 0=NO
(Normally open), 1=NC (Normally closed)
63
Manual/Auto heating output signal: 0=Off,
1=Manual, 2=Auto
64
Manual/Auto cooling output signal: 0=Off,
1=Manual, 2=Auto
65
Manual/Auto forced ventilation: 0=Off,
1=On, 2=Auto. Can e.g. be activated from a
central system for e.g. night cooling
66
Manual/Auto control of change-over mode:
0=Heating control, 1=Cooling control,
2=Automatic change-over depending on an-
alogue temperature sensor or digital input
67
Heating output signal in manual mode
68
Cooling output signal in manual mode
69-72
No function for this model
73
Selection of heating output function (NO/
NC): 0=NC, 1=NO
74
Setpoint display at setpoint adjustment:
0=The offset is shown in the display, 1=The
active setpoint + offset are shown in the
display. HEAT or COOL is shown depen-
ding on whether the unit controls according
to the heating or cooling setpoint when you
enter the menu, 2=The heating setpoint
+ offset are shown in the display, 3=The
cooling setpoint + offset are shown in the
display
This product carries the CE mark.
For more information, see www.regincontrols.com.