4 EN – Quick installation guide

Check if capacitors need to be reformed

Reform the capacitors if the drive has not been powered up (either in storage or
unused) for a year or more.
You can determine the manufacturing date from the serial number, which you find on
the type designation label attached to the drive. The serial number is of format
XYYWWRXXXX. YY and WW tell the manufacturing year and week as follows:
YY:
17, 18, 19, ... for 2017, 2018, 2019,
WW:
01, 02, 03, ... for week 1, week 2, week 3,
For information on reforming the capacitors, see Converter modules with
EN
electrolytic DC capacitors in the DC link capacitor reforming instructions
(3BFE64059629 [English]), available on the Internet at
DA
www.abb.com/drives/documents.
DE
Data
ES
IEC ratings
FI
ACQ580-31-
FR
3-phase U
= 400 V
N
09A5-4
FR
12A7-4
018A-4
026A-4
NL
033A-4
039A-4
PL
046A-4
062A-4
PT
073A-4
088A-4
RU
106A-4
145A-4
SV
169A-4
206A-4
TR

Select the power cables

ZH
See
Data
on page 4.
Ensure cooling
See
Data
on page 4. No condensation or frost is allowed. The allowed operating
temperature range of the drive without derating is -15 to +40 °C.
2
Cable
Cu (mm
)
3×2.5+2.5
170M1561
3×2.5+2.5
170M1561
3×2.5+2.5
170M1563
3×6+6
170M1563
3×10+10
170M1565
3×10+10
170M1565
3×16+16
170M1566
3×25+16
170M1567
3×35+16
170M1568
3×50+25
170M1568
3×70+35
170M1569
3×95+50
170M1570
3×120+70
170M5809
3×150+70
170M5810
...
...
aR fuse
Losses
(W)
226
329
395
579
625
751
912
1088
1502
1904
1877
2963
3168
3990
3AXD00000586715