Obey The Safety Instructions; Check If Capacitors Need To Be Reformed - ABB ACS880-31 Schnellinstallationsanleitung

Ultra-low harmonic single drive-frequenzumrichter
Vorschau ausblenden Andere Handbücher für ACS880-31:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 27
EN – Quick installation guide
This guide briefly describes how to install the drive. For complete information on
installation, see ACS880-31 drives hardware manual (3AXD50000045933 [English]).
For start-up instructions, see ACS880 drives with primary control program quick
start-up guide (3AUA0000098062 [English]).
To read a manual, go to
number.

Obey the safety instructions

WARNING! Obey these instructions. If you ignore them, injury or death, or
damage to the equipment can occur:
• Only qualified electrical professionals are allowed to install and maintain the
drive.
• Never work on the drive, motor cable or motor when main power is applied. If
the drive is already connected to the input power, wait for 5 minutes after
disconnecting the input power.
• Never work on the control cables when power is applied to the drive or to the
external control circuits.
• Do not connect the drive to a voltage higher than what is marked on the type
designation label.
• Always ground the drive, the motor and adjoining equipment to the protective
earth (PE) bus of the power supply.
• Frames R6 and R8: The drive module is heavy and its center of gravity is high.
Use a lifting device for lifting. Do not tilt the drive. Manual lifting, or overturning due
to the tilting, can cause physical injury. Make sure that the wall and the fixing
devices can carry the weight.
• Make sure that debris from drilling, cutting and grinding does not enter the drive.
• Make sure that the floor below the drive and the wall where the drive is installed
are non-flammable.

Check if capacitors need to be reformed

If the drive has not been powered (either in storage or unused) for over three years,
you must reform the capacitors.
You can determine the manufacturing date from the serial number, which you find on
the type designation label attached to the drive. The serial number is of format
MYYWWRXXXX. YY and WW tell the manufacturing year and week as follows:
www.abb.com/drives/documents
EN – Quick installation guide 3
and search for the document
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis