PLEASE NOTE:
- These operating instructions must be displayed in the
immediate vicinity of the separator.
- The emptying/disposal process must be carried out exact-
ly according to the instructions.
- Only allow licensed waste collection companies to collect
the contents of the grease separator for disposal.
- Subject to technical modifications!
- Follow the accident prevention regulations!
- SMOKING IS PROHIBITED when working on or at the
opened separator due to potential biogas formation. The
separator must be emptied for the first time within 2-3
weeks of putting into service (commissioning).
4.1 Emptying intervals:
According to EN 1825, unless specified otherwise, sludge
traps and separators must be emptied, cleaned and refilled
with fresh water at least once a month and, preferably, every
two weeks.
Attention: Correct functioning is only ensured if the separa-
tor is emptied in good time.
For this reason, a disposal (collection) contract should be
concluded with a licensed waste management company. If
possible, the emptying/collection work should be carried
out outside of business hours. Unpleasant odours must be
expected when the separator tank is opened.
Disposal
4.2 Performing the disposal
Use the removal key supplied to undo and remove the
screws and to lift in and out the cover.
- Undo the screws. Remove the cover.
- Empty the sludge trap and separator tank using the suc-
tion spout of the disposal vehicle.
- Clean the tank walls, remove and dispose of grease res-
idues.
- Fill the tank with water.
- Clean and check the seal of the cover.
- Close the cover.
23