Technical Specifications

ZAPTEC Pro is an alternating current wall
or column-mounted charging station in
accordance with IEC 61851-1, EVSE mode 3.
Dimensions and weight
H: 392 mm W: 258 mm D: 1 12 mm
Weight: approx. 5 kg (including backplate)
Installation circuit
Max. 63A serial fuse on installation circuit
for charging stations.
Backplate connection box
Cable cross section 2.5–10 mm
Cable diameter 10–20mm
Installation network, Voltages
TN, IT and TT
230VAC ±10%
400VAC ±10%
Max. current and charging output
7.36kW* at 32A/1-phase
22kW* at 32A/3-phase (applicable to TN
networks only)
5W at standby
Fuses
Built-in 3 x 40A fuses type C
Charging point
EC 62196-2 Type 2 Female with
integrated self-closing cover
Earth fault protection
Built-in type B RCD
Calibration and a self-test are carried out
before the start of every charging cycle. RCD
can be automatically reset by disconnecting
from the charging connector.
Integrated Power Meter
MID tested and calibrated (EN.50470).
Theft protection
The front cover of the ZAPTEC Pro can only be
opened using a special tool. The charging cable
can be locked permanently to the charging
station.
6
2
2
Load balancing
Together with other ZAPTEC Pro charging
stations, available power in the installation
will be distributed automatically between the
devices and phases.
Phase balancing
The charging station will dynamically select any
single phase or 3-phase in a system with other
ZAPTEC Pro charging stations, depending on
the available power.
Communications interface and cloud
connection/network
4G LTE-M1 (subscription required)
Wi-Fi 2.4 GHz, IEEE 802.1 1 b/g/n (channels 1-1 1)
Powerline (PLC) – HomePlug Green PHY®, 10
Mbit/s
Identification and configuration
Bluetooth Low Energy (BLE 4.1)
RFID/NFC reader – Mifare Classic, Type A
PLC for vehicle interface for future services as
defined by ISO151 18
Standards and approvals
CE compliance in accordance with the Radio
Equipment Directive
2014/53/EU and ROHS Directive 201 1/65/
EU, and compliance with IEC 61851-1 (TUV
SÜD) and IEC 61851-22
Temperature range
–30°C to +50°C
Degree of protection
IP54, indoor and outdoor use
IK10 impact protection
UL94 5VB flammability rating
UV resistant
Electrical protection
Protection class II (4kV AC and
6kV impulse, insulation)
Overvoltage category III (4kV)
Integration services
Third-party integration alternatives
(API, Webhooks)