INSTALLATION INSTRUCTIONS
Reinstate the conversion plug by screwing it clockwise until
it bottoms out.
NOTE:
Do NOT adjust and/or alter any components marked
with tamper indicating paint.
Conversion Plug
Conversion Plug
Figure 21: Conversion from one gas to another
Minimum Gas Flow Adjustment
(Vented Units Only)
1. Set the control into low fire setting by turning the motor
knob to OFF position and back until the valve opens.
2. The minimum rate can be set either by screwing in a cali-
brated minimum rate screw (fixed orifice) or an adjustable
minimum rate screw. Controls with adjustable screws
without a customer specific setting are factory set at maxi-
mum flow.
3. Turn the screw clockwise
flow.
4. Care should be taken to screw the fixed orifice until it
stops.
5. Close pressure tap(s) by turning the screw(s) full clockwise
. Check all connections/pressure tap(s) for leaks.
Changing the Fuel Type
(Vented Units Only)
GV60 is suitable for all gas types and can be converted to
meet the manufacturer's requirements for a specific gas type.
Adjustments of pressure regulator, minimum rate and pilot
gas are according to above-mentioned instructions. To con-
vert for LPG CE it is necessary to block the pressure regulator
by turning the regulator adjustment screw fully to the bottom
limit (or the throttle adjustment screw fully to the upper limit).
NG position
180°
LP position
to decrease the minimum
13 / 20
FOR OEM USE ONLY

FINAL CHECK

Observe several complete cycles to ensure proper opera-
tion. During these cycles the electronics will determine the
optimum ignition sequence timing.
1. STOP! Read the safety information included before pro-
ceeding.
2. Turn main valve knob to the OFF, full clockwise
position.
3. Place ON/OFF switch (if equipped) to the O (OFF position).
4. Wait five (5) minutes to clear out any gas. Verify that no
gas is in the area around the appliance, including near
the floor. If you detect gas STOP! Follow "WHAT TO
DO IF YOU SMELL GAS" in the safety information
(page 2). If no gas is present, proceed according to the
Mertik Maxitrol Operating Instructions.
FIRE OR EXPLOSION HAZARD. Attempted disassembly
or repair can cause property damage, severe injury or
death. Do NOT disassemble the gas valve; it contains no
serviceable components.