Herunterladen Inhalt Inhalt Diese Seite drucken

Toshiba RAV-SM2244AT7 Installationshandbuch Seite 26

Außengerät (split-typ)
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 54
Digital Inverter
Are there scratches or dents on the existing pipes?
Is it possible to operate the existing air conditioner?
• After the existing air conditioner is operated in cooling
mode for approx. 30 minutes or longer,* recover the
refrigerant.
• For cleaning the pipes and recovering oil
• Refrigerant recovery: Refrigerant recovery equipment
• Remove the existing air conditioner from the piping and
carry out flushing (nitrogen pressure 0.5 MPa) to remove
any remains inside of the pipe.
Note]
In case of twin pipes, also be sure to flush the
branching pipe.
Was largely discolored oil or a large quantity
of remains discharged? (When the oil
deteriorates, the color of the oil changes to a
Connect the indoor/outdoor units to the existing pipe.
• Use a flare nut attached to the main unit for the
indoor/outdoor units. (Do not use the flare nut of the
existing pipe.)
• Re-machine the flare machining size to size for R410A.
When using a Ø19.1 mm pipe for the gas pipe of the first
branching pipe
Turn the existing pipe switch on the cycle control P.C.
board of the outdoor unit to ON side. At shipment from
factory OFF
below.) (Be sure to set the contents in the table below
in order to restrict the refrigerating cycle pressure of
the equipment in the pipe standard.)
Existing pipe SW
Bit 3 of SW802
• (Airtight test), Vacuum dry, Refrigerant charge, Gas leak
check
EN
NO
YES
muddy or black color.)
NO
ON for existing pipe (Refer to the table
Switch
ON
Trial run
YES
Existing pipes: Cannot be used.
• Use new pipes.
NO
Nitrogen gas pressure 0.5 MPa
(If there is discharge of remains, it is judged that a
large quantity of remains are present.)
YES
Clean the pipes or use new pipes.
Piping necessary to change the flare nut/
machining size due to pipe compression
1) Flare nut width: H
Copper pipe
outer
diameter
H
For R410A
For R22
2) Flare machining size: A
Copper pipe
A
outer
diameter
For R410A
For R22
Becomes a little larger for R410A
Do not apply refrigerator oil to the flare surface.
25
Ø6.4
Ø9.5
Ø12.7
Ø15.9
17
22
26
29
Same as above
24
27
Ø6.4
Ø9.5
Ø12.7
Ø15.9
9.1
13.2
16.6
19.7
9.0
13.0
16.2
19.4
(mm)
Ø19.1
36
Same as
above
(mm)
Ø19.1
24.0
23.3

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Inhaltsverzeichnis