4.

DIMENSIONS AND WEIGHTS

The adhesive label on the package indicates the total weight of the panel.
5.

WARNINGS

5.1
Read this documentation carefully before installation.
It is indispensable to have the electric system and connections made by skilled personnel, in possession
of the technical qualifications indicated by the safety standards concerning the design, installation and
maintenance of technical plants, in force in the country where the product is to be installed.
Failure to comply with the safety regulations not only causes risk to personal safety and damage to the
equipment, but invalidates every right to assistance under guarantee.
5.2
The term skilled personnel means persons whose training, experience and instruction, as well as their
knowledge of the respective standards and requirements for accident prevention and working
conditions, have been approved by the person in charge of plant safety, authorising them to perform all
the necessary activities, during which they are able to recognise and avoid all dangers. (Definition for
technical personnel IEC 364).
5.3
Check that no damage has been done during transport or storage. In particular, ensure that the external
casing is perfectly entire and in excellent condition; all the internal parts of the panel (components,
leads, etc.) must be completely free from traces of damp, oxide or dirt. Clean carefully and check the
efficiency of all the components in the panel; if necessary, replace any parts that are not perfectly
efficient It is indispensable to ensure that all the leads in the panel are correctly secured to their
terminals. In the event of long storage (or in the event of replacement of any part) it is advisable to
carry out on the panel all the tests indicated by standards EN 60204-1.
6.

RESPONSIBILITY

The Manufacturer does not ensure good operation of the panel if it is tampered with or modified or made to operate at
values beyond the data on the plate.
The Manufacturer also declines all responsibility for possible errors in this booklet, if due to misprints or errors in
copying. The company reserves the right to make any modifications to products that it may consider necessary or
useful, without affecting the essential characteristics.
7.

INSTALLATION

Scrupulously respect the electric supply values indicated on the electric data plate.
The electric panels must be installed on dry surfaces, free from vibrations. Although they have a degree of protection of
IP55, it is not advisable to use them in an atmosphere with a large content of oxidising or corrosive gases.
If installed in the open, the panels must be protected as much as possible against direct sunlight. Suitable steps must be
taken to keep the internal temperature of the panel within the "environment temperature field of use" given below. High
temperatures lead to rapid ageing of all the components, causing more or less severe malfunctions.
It is also advisable for the person who installs the panels to ensure that the cable clamps are watertight.
Use the cable clamp gripping rings provided to block the power cables (of the panel, the electropump, the floats), so as
to prevent the cable clamps from working loose. As standard supply, the panels are provided with four brackets for
fixing them on the wall. It is recommended to fix them to the wall using only the slots provided in the brackets, without
making unnecessary holes in the box, so as not to affect the degree of protection of the panel and its functionality.
8.

TECHNICAL DATA

8.1

Data plate values

 Frequency:
 Number of pumps that can be connected:
 Field of use environment temperature:
 Storage environment temp. limit:
 Relative humidity (without condensation) :
 Max. altitude:
 Degree of protection:
 Panel construction:
ENGLISH
50-60 Hz
1
-10°C +40°C
-25°C +55°C
50% at 40°C MAX (90% at 20°C )
3000 m (a.s.l.)
IP55
in accordance with EN 60204-1 and EN 60439-1
16