AVENTICS | Bus Coupler AES/Valve Driver AV, PROFIBUS DP | R412018135–BAL–001–AG
Submodule status: This diagnostic message is only generated by the bus coupler. The bus coupler
checks the status of each module and can also report the following errors:
Error in electronics power supply (UL)
Error in the actuator voltage (UA)
Backplane error
The module status message consists of 22 bytes.
The header for the module status consists of 4 bytes.
Table 14:
Assignment of bytes 1-4 (header)
Byte no.
Meaning
Byte 1
Length of the diagnostic block (0x16)
Byte 2
Status type (0x82)
Byte 3
0
Byte 4
0
In the following 16 bytes, the statuses of the individual modules are listed. Each module has 2 bits
of status information. the meaning of the statuses of bit 0 and bit 1 can be found in Table 15 taking
module no. 1 for example.
Table 15:
Assignment of bytes 5-20 (module status)
Byte no.
Bit no.
Slot
Byte 5
Bit 0–1
Module no. 1
Bit 2–3
Module no. 2
Bit 4–5
Module no. 3
Bit 6–7
Module no. 4
...
...
...
Byte 20
Bit 6–7
Module no. 64
This is followed by 2 more bytes added by the bus coupler. In these bytes, the bits have the following
meanings:
Table 16:
Assignment of bytes 21–22 (messages from the bus coupler)
Byte no.
Bit no.
Byte 21
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Byte 22
Bit 0
Bit 1
Bit 0
Meaning
0
0
Module is configured correctly
1
0
An incorrect module is configured at this
module position, or the module has not been
configured at all.
1
1
A module is configured at this module
position, but no module is present (there are
more modules configured than physically
present).
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
Slot
Actuator voltage UA < 21.6 V (UA-ON)
Actuator voltage UA < UA-OFF
Logic voltage UL < 18 V
Logic voltage < 10 V
Internal error
Short-term communication malfunction in the backplane of the valve zone
PLC Configuration of the Valve System
81