100
AVENTICS | Bus Coupler AES/Valve Driver AV, PROFIBUS DP | R412018135–BAL–001–AG
Conversion of the Valve System
12
Bridge cards have the sole function of bridging the pressure supply areas. They are therefore not
taken into account during PLC configuration.
Bridge cards are available in long and short versions:
The long bridge card is always located directly on the bus coupler. It bridges the transition plate and
the first pneumatic supply plate.
The short bridge card is used to bridge additional pneumatic supply plates.
12.2.8

UA-OFF monitoring board

The UA-OFF monitoring board is an alternative to the short bridge card in the pneumatic supply plate
(see Fig. 14 on page 99).
The electrical UA-OFF monitoring board monitors the actuator voltage UA for status UA < UA-OFF.
All voltages are directly passed through. The UA-OFF monitoring board must therefore always be
installed after an electrical supply plate to be monitored.
In contrast to the bridge card, the UA-OFF monitoring board has to be taken into account when
configuring the control.
12.2.9

Possible combinations of base plates and cards

Valve driver boards, 4x, are always combined with two 2x base plates. Table 25 shows the possible
combinations of base plates, pneumatic supply plates, electrical supply plates, and transition plates
with various valve driver boards, bridge cards, and supply boards.
Table 25:
Possible combinations of plates and cards
Base plate
Base plate, 2x
Base plate, 3x
Two base plates, 2x
Pneumatic supply plate
Transition plate and pneumatic supply plate
Electrical supply plate
1)
Two base plates are linked with a valve driver board.
The boards in the AV-EP base plates are installed permanently and can therefore not be
combined with other base plates.

12.3 Identifying the modules

12.3.1

Material number for bus coupler

The bus coupler can be clearly identified using its material number. When exchanging the bus
coupler, you can use the material number to reorder the same unit.
The material number is printed on the rating plate (12) on the back of the device and on the top below
the identification key. The material number for the AES series bus coupler for PROFIBUS DP is
R412018218.
Circuit boards
Valve driver board, 2x
Valve driver board, 3x
1)
Valve driver board, 4x
Short bridge card or UA-OFF monitoring board
Long bridge card
Supply board