Herunterladen Inhalt Inhalt Diese Seite drucken

Reviewing The Valve Zone Conversion - Aventics AES Serie Systembeschreibung

Buskoppler aes/ventiltreiber av; profibus dp
Vorschau ausblenden Andere Handbücher für AES Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
AES-
D-BC-
PDP
UA
P
B
Fig. 18: Examples for impermissible configurations
AVENTICS | Bus Coupler AES/Valve Driver AV, PROFIBUS DP | R412018135–BAL–001–AG
A
A
B
AES-
D-BC-
PDP
UA
P
12.5.4

Reviewing the valve zone conversion

Following the conversion of the valve zone, use the following checklist to determine whether you
have complied with all rules.
 Have you mounted at least 4 valve positions after the first pneumatic supply plate?
 Have you mounted a maximum of 64 valve positions?
 Have you integrated no more than 32 electrical components? Note that an AV-EP pressure
regulator corresponds to three electrical components.
 Have you mounted at least two valves after every pneumatic or electrical supply plate that marks
the start of a new section?
 Have you always installed the valve driver boards to be in line with the base plate limits, i.e.
– One base plate, 2x, is installed with one valve driver board, 2x,
– Two base plates, 2x, are installed with one valve driver board, 4x,
– One base plate, 3x, is installed with one valve driver board, 3x,
 Have you integrated no more than 8 AV-EPs?
If you have answered "Yes" to all these questions, you may proceed with the documentation and
configuration of the valve system.
P
UA
B
AES-
D-BC-
PDP
UA
Conversion of the Valve System
UA
P
UA
107

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Av serie

Inhaltsverzeichnis