for instance, the above requirements will be met if you use flues for pressure exhaust of flue gases (the con-
densation kind).
Make sure the air intake tube's inlet is positioned so that it is not likely to be obstructed by foreign matter and,
where necessary, use suitable screens.
The temperature of the incoming air must not exceed 40 °C;
The inside diameter of the hose must be at least 80 mm.
The intake tube can be up to 6 metres in length.
Warning: length is reduced if there are bends in the intake section.
For instance, using a tube with a smooth inside surface, you must allow for the following losses:
- for each 45° bend, tube length is reduced by 0.5 m;
- for each 90° bend, tube length is reduced by 0.8 m.
BURNER INSTALLATION MUST COMPLY WITH ONE OF THE INSTALLATIONS ILLUSTRATED IN THE FIG-
URES BELOW.
ATTENTION
Under no circumstances should the air's entry in the hose intake area be obstructed.
The hose must not be blocked in any way or feature a shutting device (valves, membranes etc.).
Coaxial tubes must not be installed for any reason.