System test
Indoor unit fault codes
The indoor unit can detect any system fault and stop it
at once. The failure is recoverable based on the table
below. When a diagnostic is active, the green LED
(P) and the yellow LED (R) blink 0,1 seconds on, 0,1
seconds off and indicate a fault code.
The yellow LED (R) indicates the tens digits.
The green LED (P) indicates the unit digits.
Two seconds elapse between the yellow LED and the
green LED lighting.
The sequence ends with both LEDs off for 4 seconds.
Example:
Fault code 12
• The yellow LED blinks (it indicates the tens digits).
• Both LEDS are off for 2 seconds.
• The green LED blinks twice with a 0,5 seconds fre-
quency.
• Both LEDS are off for 4 seconds.
The fault sequence described above is repeated until
the fault has been repaired. If the fault code is lower
than 10, the yellow LED (R) is not blinking.

Address selector

If you are installing two indoor units in the same room and you want them to operate in independent mode, it is
necessary to assign each unit its own address so that each unit can operate via its own remote control.
This configuration procedure is not mandatory but may be necessary depending on installation requirements.
For display and remote control button reference see the remote control manual.

Unit configuration

2
3
4
7
1
Press [4] and [7] buttons of the infrared remote
1
control and hold them pressed for more than
5 seconds. The display will be cleared, [S] will
display the first configuration item (rAdr = remote
address) and [C] will display the default value
of this configuration item (Ab = control of both
indoor units).
Press either the [2] and [3] buttons to change the
2
default value (Ab) to the new value (A) or (b).
Press button [7] to send the configuration
3
message to the unit
Press button [1] to leave the configuration menu
4
or do not press any buttons for more than 30 sec.
7
38XPS - 38XP-
A
D
A
S
B
B
Code Description
2
Condensate Pump Failure or water drain Failure
3
Indoor unit Room Air sensor fault
4
Indoor unit Tc Coil sensor fault
8
Matching between outdoor unit and indoor unit not
admitted
10
Indoor unit software fault (EEProm Corrupt)
12
Indoor unit software fault (Address / Zone Corrupt)
14
Loss of Signal From CDU
15
Indoor unit Tcj Coil sensor fault
17
Outdoor unit TO Air sensor fault
18
Outdoor unit control box fault (G-Tr short circuit
protection)
20
Position Detection Circuit Error
21
Outdoor unit Current Sensor fault
22
Outdoor unit Heat Exchange Sensor fault
23
Outdoor unit Discharge Temperature Sensor fault
24
Outdoor unit Fan fault
26
Other Outdoor unit fault
27
Outdoor unit Compressor Lock
28
Outdoor unit Discharge Temperature fault
29
Outdoor unit Compressor Breakdown
30
Other Outdoor unit fault
31
Outdoor unit High Temperature/Pressure Release

Remote configuration

2
3
4
7
1
Press [3] and [7] buttons of the infrared remote
1
control and hold them pressed for more than
5 seconds. The display will be cleared, [C] will
display the first configuration item (CH = remote
address) and [S] will display the default value
of this configuration item (Ab = control of both
indoor units).
Press either the [2] and [3] buttons to change the
2
default value (Ab) to the new value (A) or (b)
Press button [7] to send the configuration
3
message to the unit.
Press button [1] to leave the configuration menu
4
or do not press any buttons for more than 30 sec
A
C
D
A
S
B
B

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Xpower inverter 38xpsXpower inverter 38xp-

Inhaltsverzeichnis