40KQM

Address selector and fault code

Address selector
If you are installing two indoor units in the same room and you want
them to operate in independent mode, it is necessary to assign
each unit its own address so that each unit can operate via its own
remote control.
For configuration, proceed as follows:
Configuration (of the unit)
• Press the
and
buttons of the infrared remote control and
hold them pressed for more than 5 seconds.
• The display will be cleared, the time segments will display the
first configuration item (rAdr = remote address) and the
temperature segments will display the default value of this
configuration item (Ab = control of both indoor units).
• Press either the
or
button to change the default value (Ab)
to the new value (A) or (b).
• Press
button repeatedly until "UAdr" is displayed.
• Press either the
or
button to change the default value of
CCN unit address (1) to the new value (1÷240).
• Press
button repeatedly until "ZONE" is displayed.
• Press either the
or
button to change the default value of
Zone number (0) to the new value (0÷240).
• Press
button repeatedly until "A St" is displayed.
• Press either the
or
button to change the default value of
auto restart in last mode (On) to the new value of start in OFF
mode (OF).
• LOOK OUT!
Whichever configuration value changed must be transmitted
to the indoor unit pressing
• Press
button to leave the configuration menu.
Configuration (of the remote controller)
• Press the
and
buttons of the infrared remote control and
hold them pressed for more than 5 seconds.
• The display will be cleared, the temperature segments will
display the first configuration item (CH = remote address) and
the time segments will display the default value of this
configuration item (Ab = control of both indoor units).
• Press either the
or
button to change the default value (Ab)
to the new value (A) or (b).
• Press
button repeatedly until "tU" is displayed.
• Press either the
or
button to change the default value of
temperatures in Degrees Celsius (C) to the new value Degrees
Fahrenheit (°F).
• Press
button repeatedly until "Hr" is displayed.
• Press either the
or
button to change the default value of
Maximum heating set point temperature admitted in Degrees
Celsius (32) or Degrees Fahrenheit (90) to the new value
Degrees Celsius (17÷32) or Degrees Fahrenheit (63÷90).
• Press
button repeatedly until "Cr" is displayed.
• Press either the
or
button to change the default value of
minimum cooling set point temperature admitted in Degrees
Celsius (17) or Degrees Fahrenheit (63) to the new value Degrees
Celsius (17÷32) or Degrees Fahrenheit (63÷90).
• Press
botton repeatedly until "CL" is displayed.
• Press either the
or
button to change the default value of
Time format as AM/PM (12) to the new value of 24 hours time
format (24).
• LOOK OUT!
Whichever configuration value changed must be confirmed
pressing
button each time.
• Press
button to leave the configuration menu.
GB - 14
button each time.
Note:
When 30 seconds have elapsed and no buttons have been
pressed, the remote control will automatically exit the
configuration menu and the procedure has to be restarted.
Fault code
The inside unit can detect any system fault and stop it at once.
The failure is recoverable based on the table VI below.
When a diagnostic is active, the green LED (P) and the yellow
LED (R) blink 0.1 seconds on, 0.1 seconds off and indicate a fault
code.
The yellow LED (R) indicates the tens digits.
The green LED (P) indicates the unit digits.
Two seconds elapse between the yellow LED and the green LED
lighting.
The sequence ends with both LEDs off for 4 seconds.
Example:
Fault code 12
• The yellow LED blinks (it indicates the tens digits).
• Both LEDS are off for 2 seconds.
• The green LED blinks twice with a 0,5 seconds frequency.
• Both LEDS are off for 4 seconds.
The fault sequence described above is repeated until the fault has
been repaired.
If the fault code is lower than 10, the yellow LED (R) is not
blinking.
Table VI
Code Description
2
Condensate Pump Failure or water drain Failure
3
Indoor unit Room Air sensor fault
4
Indoor unit Tc Coil sensor fault
10
Indoor unit software fault (EEProm Corrupt)
12
Indoor unit software fault (Address / Zone Corrupt)
14
Loss of Signal From CDU
15
Indoor unit Tcj Coil sensor fault
18
Outdoor unit control box fault (G-Tr short circuit protection)
20
Position Detection Circuit Error
21
Outdoor unit Current Sensor fault
22
Outdoor unit Heat Exchange Sensor fault
23
Outdoor unit Discharge Temperature Sensor fault
24
Outdoor unit Fan fault
26
Other Outdoor unit fault
27
Outdoor unit Compressor Lock
28
Outdoor unit Discharge Temperature fault
29
Outdoor unit Compressor Breakdown
31
Outdoor unit High Temperature/Pressure Release
In case of malfunction, record the fault code, turn the system off,
disconnect the mains power supply and contact a qualified service
engineer.