Herunterladen Inhalt Inhalt Diese Seite drucken

Helios B VD Montage- Und Betriebsvorschrift Seite 55

Brandgas-dachventilatoren in temperaturklassen f400/f600
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and Operating Instructions
Interval
Test and maintenance work
Annual
Measurement and evaluation of bearing conditions with
bearing condition diagnostics.
Annual
Check fan vibration state.
Annual
Check impeller for imbalance.
5 years
Replace motor bearings.
"According
Replace motor bearings.
to status dis-
play of LZD,
but no later
than after 10
years
No time limit,
Replace motor bearings.
only after war-
ning on status
display of LZD
According
Replace defective, damaged and worn parts/compo-
to status
nents on fan suspension, fan, drive motor, cooling air
fan, protection devices, attachments and accessories as
required.
See motor
Regrease motor bearings with regreasing device.
type plate
B VD – Smoke exhaust roof fans F400/F600
23
Fan B VD F400/F600
Standard
incl . LZD
Basic
x
x
x
x
x
x
x
x
x
x
x
x
To be carried out by
incl . LZD
Comfort
x
Specialist
x
Specialist
x
Specialist
Manufacturer or specialist
company authorised by
the manufacturer
Manufacturer or specialist
company authorised by
the manufacturer
x
Manufacturer or specialist
company authorised by
the manufacturer
x
Specialist
x
Specialist
EN