Herunterladen Inhalt Inhalt Diese Seite drucken

Wiring Diagram Overview - Helios B VD Montage- Und Betriebsvorschrift

Brandgas-dachventilatoren in temperaturklassen f400/f600
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and Operating Instructions
CHAPTER 6
WIRING DIAGRAM
OVERVIEW
SS-1262
3~ motor with RS 6+1+2 7,5
(with Y bridge)
B VD with nominal output ≤ 2,20
kW (direct startup or FU operation)
B VD – Smoke exhaust roof fans F400/F600
6 .0
Wiring diagrams
The following table describes the fan start-up and indicates the required connection line:
Operation
Voltage specification
at
on motor type plate
400 V, 3~
230 / 400 V
400 / 690 V
Customer-side
Connection cable
Cable Motor prot .
with TK/PTC
*Clarify direct startup with the local network operator before commissioning!
≥ 3,0 kW Dir. startup Y P
Y/ △ - startup P
M
Y
No
Yes
6 + PE
2
M
17
Single-speed
Fan start-up
≤ 2,2 kW
Dir. startup △ P
M
Yes
No
3 + PE
2
3~ Motor
mit TB/TP (TK/KL)
9
RS 6+1+2 7,5
85499 022 SS-1262 18.06.19
EN
≤ 2,2 kW
M
No
Yes*
3 + PE
2