Herunterladen Inhalt Inhalt Diese Seite drucken

Hitachi YUTAKI Serie Bedienungsanleitung Seite 25

Vorschau ausblenden Andere Handbücher für YUTAKI Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 43
ElECTrIC WIrInG
10.3 COMMON WIRING
!
C A U T I O N
All the field wiring and electrical components must comply with local
codes.
10.3.1 Electrical wiring between indoor unit
and outdoor unit
Connect the electrical wires between the indoor unit and the
outdoor unit, as shown below.
follow local codes and regulations when performing
electrical wiring.
Use twist pair wire (more than 0.75 mm²) for operation wiring
between outdoor unit and indoor unit.
Use 2-core wire for the operating line (Do not use wire with
more than 3 cores).
Use shielded wires for intermediate wiring to protect the
units from noise obstacle at length of less than 300 m and
size complied with local code.
open a hole near the connection hole of power source
wiring when multiple outdoor units are connected from one
power source line.
The recommended breaker sizes are detailed in the Wire
size section.
In the case that a conduit tube for field-wiring is not used, fix
rubber bushes with adhesive on the panel.
All the field wiring and equipment must comply with local and
international codes.
H-lInK twist pair shielded cable must be grounded in the
outdoor unit side.
10.3.2 Wire size and main switch protection
Recommended minimum sizes for field provided wires and select the main switches according to the next table:
Model
rAS-4WHVnPE
rAS-5WHVnPE
rAS-6WHVnPE
rAS-4WHnPE
rAS-5WHnPE
rAS-6WHnPE
rAS-8WHnPE
rAS-10WHnPE
N O T E
Follow local codes and regulations when selecting field wires, Circuit breakers and Earth Leakage breakers
Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord (code designation H05RN-F)
15
PMML0372B rev.1 - 03/2016
Power source
cable size
Power supply
EN60 335-1
1~ 230V 50Hz
6.0 mm
2.5 mm
3n~ 400V 50Hz
4.0 mm
6.0 mm
!
C A U T I O N
Pay attention to the connection of the operating line. Incorrect
connection may cause the failure of PCB.
Check to ensure that the field supplied electrical components
(mains power switches, circuit breakers, wires, connectors and wire
terminals) have been properly selected according to the electrical
data indicated on this chapter and they comply with national and local
codes. If it is necessary, contact with your local authority in regards to
standards, rules, regulations, etc.
3N~400V /
50 Hz
3N~400V /
50 Hz
Terminal board
Circuit Breaker
Earthleakage Breaker
field Wiring
field supplied
optional Accessory
Transmitting
cable size
MC (A)
EN60 335-1
2
0.75 mm²
2
2
2
outdoor unit
L1 L2 L3
L1 L2 L3
N
N
operating line
(Shielded Pair Cable)
5V (non-Pole Transmission,
H-lInK System)
Indoor Unit
CB (A)
ELB
30
32
30
32
2/40/30
30
32
14.0
15
14.0
15
16.0
20
4/40/30
24.0
25
24.0
25

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis