OJ Zone Module and Room Panel with 2" Touchscreen
PI regulator
Regulation is based on a proportional-integral controller. The
P-band (measured in delta Kelvin) and the I-time for VAV damper,
cooling valve and heating valve can be tuned to fit specific needs.
The default settings will suit most systems and should only be
changed if absolutely necessary. The regulator values can be
adjusted by tapping the PI regulator button.
Choose either P-band or I-time by tapping the respective button.
The value shown under P-band is the OJ Electronics default value.
The minimum P-band value is 1° Kelvin and the maximum value is
10° Kelvin. Settings can be chosen in steps of 1° Kelvin.
18
© 2015 OJ Electronics A/S
English
OJ Zone Module and Room Panel with 2" Touchscreen
The minimum I-time value is 10 seconds and the maximum value
is 999 seconds. Settings can be chosen in steps of 1 second. The
values shown below are the OJ Electronics default values.
Tap the Up or Down arrow to select the required value. Tap the
Accept button to confirm your choice.
After changing the I-time values, tap the Left arrow six times to go
back to the main menu. In the main menu, tap Home to exit the
menu.
© 2015 OJ Electronics A/S
English
19