Herunterladen Inhalt Inhalt Diese Seite drucken

ABB PowerValue 11 RT G2 Kurzanleitung Seite 21

Vorschau ausblenden Andere Handbücher für PowerValue 11 RT G2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 24
T R O U B L E S H O OT I N G
Alarm or Event
BUS Over Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F021
BUS Under Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F022
BUS Unbalance
Fault (Red) LED is On.
Beep continuous.
Code: F023
BUS Short
Fault (Red) LED is On.
Beep continuous.
Code: F024
BUS Softstart Fail
Fault (Red) LED is On.
Beep continuous.
Code: F025
Inv Over Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F032
Inv Under Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F033
Inv Softstart Fail
Fault (Red) LED is On.
Beep continuous.
Code: F034
Charger Fail
Fault (Red) LED is flash
1 beep every 1 second
Code: A015
Battery Over Voltage
Fault (Red) LED is On.
Beep continuous.
Code: F016
Negative power Fault
Fault (Red) LED is On.
Beep continuous.
Code: F0E1
Parallel cable loss
Fault (Red) LED is On.
Beep continuous.
Code: F0E2
Possible cause
Indicates that the UPS has
bus overvoltage fault.
Indicates that the UPS has
bus undervoltage fault.
Indicates that the positive
bus voltage and negative bus
voltage are too lopsided.
Indicates that the bus
voltage is decreasing very
fast.
Indicates that the bus could
not soft start successfully.
Indicates that the UPS has
inverter overvoltage fault.
Indicates that the UPS has
inverter undervoltage fault.
Indicates that the inverter
could not soft start
successfully.
Indicates that the UPS has
confirmed the charger has
failed.
Indicates that the battery
voltage is too high.
In a parallel system, power of
UPS is negative.
In parallel system, parallel
cable disconnected.
Remedy
The UPS transfers to bypass
mode if supporting the load.
The UPS transfers to bypass
mode if supporting the load.
The UPS transfers to bypass
mode if supporting the load.
Contact your service
representative.
Contact your service
representative.
The UPS transfers to bypass
mode if supporting the load.
The UPS transfers to bypass
mode if supporting the load.
Contact your service
representative.
The UPS turns off the charger
until the next power recycle.
Contact your service
representative.
The UPS will turn off the
charger until the battery
voltage is normal.
Redundancy mode, the fault
UPS turn to fault mode
without output
Increase mode, UPS1& UPS2
turn to fault mode.
Disconnect parallel cable one
turn to fault mode.
21

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis