Mounting and installation instructions,
Illustration
Placement of the drain:
Connection of
Power is connected to the unit in accordance with the nameplate. Please see wiring
power supply
diagrams on pages 91-93.
Important! All electrical connections must be made in accordance with local power
Water quality
Instructions from the supplier of the water treatment plant must always be respected.
With the addition of
The following guidance values are applicable to swimming pools with the addition of
chemicals
chemicals
Free chlorine content
Combined chlorine content
pH
Total alkalinity
Calcium hardness
Total dissolved solids
Sulphates
supply company regulations!
Chemicals
continued
ppm
1,0-2,0
Max. 1/3 of free chlorine content
7,2-7,6
80-150
250-450
< 2000
< 360
Continued overleaf