Perform this assembly step on a flat
surface:
Lay arm 1 down flat
Pull cable (from arm) through ceiling conduit 2
Insert slide pad 3 into the groove at the top
Push ceiling conduit 2 (with boring 4 aligned
upward ) and arm 1 together
Secure slide pad 3 by screwing in the threaded
pin 5 (up to the stop)
Release threaded pin 5 by a ¼ turn maximum
and check function
Also check:
Threaded pin must now be flush
WARNING
Risk of injury from falling parts
Assembly must be performed by two people.
WARNING
Risk of injury from falling luminaire
The ceiling must be made of solid concrete to
guarantee a secure hold.
Use suitable wall anchors.
Hold the ceiling bracket against the ceiling and
strike the ceiling anchor with a hammer
Tighten fastening in line with manufacturer's
data
Place cover and end ring on the ceiling tube
Pull the light cable of the ceiling tube through
the light mount.
Insert ceiling tube into light mount
Secure using the M8 safety screw and nut 1
Tighten M8 safety screw and nut 1 (20 Nm /
14.75 lbf ft)
Tighten all 4 threaded pins 2 (5 Nm / 3.68 lbf ft)
DANGER
Mortal danger from electric shock
Disconnect from the power supply and secure
against unintended switching on before starting
work on the power connection.
Make power connection
ENG