Herunterladen Inhalt Inhalt Diese Seite drucken

Delta SOLIVIA 5.0 EU G3 Bedienungsanleitung Seite 32

Solar inverter
Vorschau ausblenden Andere Handbücher für SOLIVIA 5.0 EU G3:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 41
DISPLAY
LED STATUS
MESSAGE
green: <off>
red: <off>
Error # 302
yellow: <on>
green: <off>
Error # 506
red: <on>
Error # 508
yellow: <off>
Isolation start-
green: <on>
up warning
red: <on>
Isolation run-
yellow: <off>
ning warning
PV+ groun-
green: <on>
ding fault
red: <on>
PV- grounding
yellow: <off>
fault
green: <off>
red: <off>
Relay error
yellow: <on>
green: <off>
red: <off>
Revision error
yellow: <on>
green: <on>
Self test
red: <on>
ongoing
yellow: <on>
green: <flashes>
PV power too
red: <off>
low
yellow: <off>
green: <flashes>
PV voltage too
red: <off>
low
yellow: <off>
green: <flashes>
Synchronize
red: <off>
to AC
yellow: <off>
green: <on>
Varistor
red: <off>
warning
yellow: <flashes>
Please follow the instructions above before contacting your service technician!
30
CAUSE
The device trips and
reverts to grid input mode
once the temperature has
dropped.
Isolation resistance fault
on the DC side during
start-up phase (# 508) or
running phase (# 506).
Isolation resistance fault
on the DC side during
start-up phase or running
phase.
Connection PV+ (PV-)
to GND is interrupted or
wrong pole is connected
to GND.
One of the anti-islanding
protection output relays is
faulty / defective.
Versions of hard- and soft-
ware are not compatible.
Initialization of solar inver-
ter on start-up.
Insufficient input power.
PV generator voltage bet-
ween 100 V and 150 V.
Check grid voltage and
grid frequency for grid
input mode.
Internal varistor at the DC
input is defective.
Operation and installation manual SOLIVIA 5.0 EU G3
ELIMINATION
- Check the installation site (no direct
sunlight, air circulation).
- Check the isolation resistance on the DC
side of the PV modules.
- You must check the isolation resistance
on the DC side of the PV modules.
Solar inverter is still feeding!
- Check that the GND connection has been
made correctly and/or check the fuse in
the grounding path. Change the fuse if
necessary. The solar inverter remains in
feed-in operation.
- The solar inverter is defective.
- Return the device.
- If the fault persists after the device has
been reset, please inform your service
technician.
The first time the solar inverter is started
up:
- Normal function with a PV cell voltage
of between 100 V and 150 V.
- Insufficient insolation (dawn/twilight).
- Check the PV cell voltage via the
display in the N menu.
- Insufficient insolation.
- Check the PV cell voltage via the
display in the N menu.
- Normal function before input mode.
- Although you can, in theory, carry on
using the solar inverter, the varistors
should be replaced at the earliest oppor
tunity. This will involve returning the
device.