Herunterladen Inhalt Inhalt Diese Seite drucken

Connecting Two Genarators In Parallel - Dometic TEC29EV Montageanleitung

Vorschau ausblenden Andere Handbücher für TEC29EV:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 31
TEC29EV
10.10

Connecting two genarators in parallel

I
NOTE
Use only one starter battery to start both generators.
When connecting the generators, note the following:
 It is not possible to connect more than two generators in parallel.
 To start one generator at a time the starter battery capacity has to be
according to the generator manual (minimum capacity: 60 Ah).
To start both generators at the same time you have to double the battery
capacity.
 The cross section of the battery connection cable for each generator has
to be at least:
– 10 mm² if the total length is less than 6 m
– 16 mm² if the total length is more than 6 m
I
NOTE
 The maximum distance between each generator to the
junction box is 15 m.
 The maximum length difference between the output cables of
the generators must be 2 m.
Proceed as follows (fig. g, page 12):
➤ Connect each generator to a junction box (1; not included in the scope of
delivery).
The minimum cross section for each generator output cable is 2.5 mm².
➤ Create a single output for the load (2) inside the junction box (1).
The minimum cross section for the parallel output cable is 6 mm².
➤ Connect the battery's negative pole to ground.
➤ Connect the output ground cable to ground.
➤ Connect the change over switch AG 113 (available as accessory)
between the junction box and the load.
➤ To properly run the generators in parallel connect the inverters (4) of each
genarator using the parallel cable (3; available as accessory).
EN
Connecting the electrical power to the generator
29

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis