5. Installation and operation

5.1 Installation instructions

CAUTION!
All installation, connection, and maintenance works for the device,
ventilation, and combustion gas extraction devices must be performed
by the qualified and authorized technician according to the valid
international, national and local regulations.
Read through these instructions carefully before the installation and operation.
After receiving the device make sure that it has not been damaged during transport
and the package is not damaged. In case of damages or lack of parts it is required to
immediately inform the carrier, vendor/manufacturer and specify the article no. and
series no. (placed on the rating plate on the left external side of the device in case of
devices no. 1582001 and 1582201, or in the open base for devices no. 1582101)
and attach the photographical documentation.
Make sure that there are no elements blocking the way to the installation place
through the doors, corridors, or other communication routes.
CAUTION: The device may overturn during transport, which may damage the device
itself, other objects or cause the injuries. Use the means appropriate for the device
weight. The device should not be dragged or tilted, but lifted perpendicularly to the
ground and handled in the horizontal direction.

5.1.1 Installation

CAUTION!
According to the regulations the device must be installed only in
permanently ventilated rooms in order to prevent unacceptable
concentration of harmful combustion products in a room.
The installation room must consist as much air as required for appropriate
combustion of gas. For appropriate combustion the intake air flux must not be
lower than 2 m
device). Moreover follow the safety regulations.
Air must be taken directly from outside environment through the permanently
opened gaps or intake ducts connected with fresh air area.
- 44 -
3
/h per kW of the rated device power (see rating plate on the