COmmISSIONING
Controller menu
…„
Booster heater on/off
…„
Booster heater opening level
…„
Ext. heat generator pump
…„
Ext. heat generator pump on/off
…„
Heating circuit 1 manual mode
…„
Heating circuit 1 circulation pump
…„
Heating circuit 1
…„
Cooling circuit pump on/off
…„
Activate manual cooling mixing valve
…„
Mixing valve cooling opening level
…„
Cooling cylinder diverter valve on/off
…„
Disconnect borehole diverter valve on/off
…„
Heat surplus diverter valve on/off
…„
Pump overheating
…„
Heat surplus fan
…„
Heating circuit 2 / 3 / 4 / 5 pump on/off
…„
Heating circuit 2 / 3 / 4 / 5 mixing valve opening level
…„
DHW draw-off control – pump
…„
Opening level, DHW draw-off control – mixing valve
…„
DHW draw-off control – booster heater
…„
DHW heating system – pump unit
…„
Opening level, water charging system – mixing valve
…„
Pool diverter valve on/off
…„
Pool pump on/off
…„
Pool mixing valve opening level
…„
Manually activate expansion valve
…„
Expansion valve opening level
…„
Ignore measured operating pressure
…„
Central fault, test signal
Parameter
Actual rpm
Current speed
Activate manual test
…„
f Activate or deactivate the function to carry out the different
f
manual tests.
A hand is displayed in the controller when the manual test is
activated. The various components can be tested for their func-
tionality. All settings carried out now do not lead to any parameter
changes at the heat pump.
Observe the chapter "Commissioning / Manual test of connected
components" in the operating and installation instructions for
the heat pump.
…„
Brine pump on/off
f Activate or deactivate the function.
f
When the function is activated, the pump starts.
…„
Brine pump rpm
f Set the output at which the pump should run.
f
…„
Circulation pump (HP) on/off
f Activate or deactivate the function.
f
When the function is activated, the pump starts.
www.stiebel-eltron.com
…„
Circulation pump (HP) rpm
f Set the output at which the pump should run.
f
Ext. brine pump on/off
…„
Cannot be activated if the "Brine pump on/off" is switched on.
f Activate or deactivate the function.
f
When the function is activated, the pump starts.
Hot gas pump manual mode
…„
Can only be activated if the "Hot gas mode" function is switched
on in the "Hot gas" menu.
f Activate or deactivate the function.
f
When the function is activated, the pump starts.
…„
Hot gas diverter valve, cylinder charging
f Activate or deactivate the function.
f
When this function is activated, the diverter valve switches.
…„
Hot gas pump on/off
f Activate or deactivate the function.
f
When the function is activated, the pump starts.
…„
Diverter valve, 0=heating 1=DHW
Unit
f Set the direction in which the diverter valve should switch.
f
rpm
Booster heater on/off
…„
f Activate or deactivate the function.
f
When the function is activated, the booster heater starts.
…„
Compressor manual mode
f Activate or deactivate the function.
f
When this function is activated, the compressor starts.
…„
Compressor stage setting
Can only be adjusted if the "Compressor manual mode" function
is activated.
f Set the stage at which the compressor should run.
f
…„
Booster heater
f Activate or deactivate the function.
f
…„
Booster heater on/off
Can only be activated if the "Booster heater" function is switched
on.
f Activate or deactivate the function.
f
When the function is activated, the booster heater starts.
Booster heater opening level
…„
f Set the output level at which the booster heater should run.
f
STE |
47