When connecting the cylinder, observe the following points:
CAUTION
- Device damage. The plastic sleeves in the connections must not be removed.
CAUTION
- Device damage. Cylinders > 2000 litres are transported in a horizontal position. Only
use the devices provided for siting.
Observe the flow rule: "For water installations with two or more metals, then the base metals
must come before the noble metals in the direction of flow."
Note!
If a connection is not being used, it must be tightly closed and insulated.
Note!
For cylinders > 2000 litres, the insulation is delivered separately. Please observe the
instructions for installation of the insulation.
5.3.1

Drinking water pipe connection

WARNING
Health hazard due to lack of hygiene
Domestic hot water can be contaminated if installation work is not carried out cleanly
Fit the cylinder cleanly in accordance with best practice.
ATTENTION
Equipment damage due to incorrect installation of the safety valve.
If the safety valve is incorrectly fitted, the device can be damaged due to exceeding of the
permissible operating pressure.
Install only a type-approved safety valve.
Adjust the safety valve settings do that the permissible working pressure cannot be exceeded.
Install the drain pipe of the safety valve so that its end is positioned above a drainage point in a
frost-proof area, and is clearly visible.
The drain pipe must have at least the same cross-section as that of the safety valve outlet.
Storatherm — 25.07.2018
Installation
English — 11