Herunterladen Diese Seite drucken

ABB C575 Betriebsanleitung Seite 2

Zweihand-steuergerät
Vorschau ausblenden Andere Handbücher für C575:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Note! This product is obsolete. For replacement see Sentry safety relays.
Two-hand control unit
Operating Instructions
Read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device
before working on this device.
CAUTION
Reliable functioning of the equipment is only ensured with
certified components.
The devices must be installed in a switchgear cabinet with the IP32,
IP43 or IP54 degree of protection, depending on the ambient conditions.
IMPORTANT NOTICE
The products described herein are designed to be components of a customized
machinery safety-oriented control system. A complete safety-oriented system
may include safety sensors, evaluators, actuators and signaling components. It
is the responsibility of each company to conduct its own evalution of the effec-
tiveness of the safety system by trained individuals. ABB AG, its subsidiaries
and affiliates (collectively "ABB") are not in a position to evaluate all of the cha-
racteristics of a given system or product or machine not designed by ABB.
ABB accepts no liability for any recommendation that may be implied or stated
herein. The warranty contained in the contract of sale by ABB is the sole war-
ranty of ABB. Any statements contained herein do not create new warranties or
modify existing ones.
Applications
C575 is suitable for installation in controls for presses.
- Hydraulic presses DIN EN 693
- Eccentric and related presses EN 692
- Screw presses EN 692.
Using this device, max. Performance Level e / Cat. 4 according to
DIN EN ISO 13849-1 and / or SIL 3 according to DIN EN IEC 62061 and / or cate-
gory III C according to DIN EN 574 can be achieved. The user must carry out an
evaluation of the overall systems.
Functions and Connections
The two-hand control unit C575 possesses two release circuits in the form of NO
circuits and two signal circuits in the form of NC circuits. Five LEDs indicate the
operating status and the functions.
The release circuits are closed by simultaneous operation (< 0.5 s) of the push-
buttons S1, S2. If one pushbutton is no longer pressed, the release circuits open.
They do not close again until both pushbuttons are no longer pressed and then
simultaneously pressed again.
1. Apply the operating voltage (UB) to the terminals A1 and A2. The operating
voltage must be de-energized with the operating energy of the press.
2. Close the feedback circuit:
Connect the bridge to Y11, Y12 or NC contacts of external contactors.
3. Connect the input circuit:
Connect pushbutton S1 to terminals Y21, Y22, Y23 and
pushbutton S2 to terminals Y31, Y32, Y33.
Terminal
Operating
A1
A2
assignments
voltage
Outputs
13, 14
23, 24
31, 32
41, 42
Inputs
Y11, Y12
Y21, Y22, Y23
Y31, Y32, Y33
2
Cable lengths for 2 x 1.5 mm
Figures Fig. I:
Dimension drawings (dimensions in mm)
Fig. II:
Installation/Cage Clamp
Fig. III:
Safety data
Fig. IV:
Internal circuit:
CHANNEL 1,
Â
2
L/+
N/-
Release circuit 1 (NO)
Release circuit 2 (NO)
Signaling circuit 1 (NC)
Signaling circuit 2 (NC)
Feedback circuit
Pushbutton S1
Pushbutton S2
max. 1000 m for total cable length for sensors
Power pack,
PTC fuse,
Control logic,
¿
À
Á
CHANNEL 2,
Safety circuit
Ã
Ä
Order No.: 2CDC 113 020 M9701
Fig. V:
External circuit:
S1, S2 pushbuttons on two-hand control console
H1 Indicator light
K1, K2 contactors must be positively driven contacts
Operation
LEDs
POWER
S1 ON
S2 ON
CHANNEL 1 CHANNEL 2 Pushbutton
The unit cannot be started with the following faults:
- Short-circuit, e.g. between the pushbuttons
- Defective relay coils
- Conductor failure
- Welded contacts
The output relays do not pick up if
- the pushbuttons are not pressed simultaneously (< 0.5 s)
- only one pushbutton is pressed
- the feedback circuit Y11, Y12 is open.
Technical Data
Permissible ambient temperature T
u
Operation / storage
Degree of protection to DIN EN / IEC 60529 IP20
Rated insulation voltage U
i
Rated impulse withstand voltage U
imp
Rated control supply voltage U
s
Rated power
AC / DC operating range
Shock resistance (half-sine) as per
DIN EN / IEC 60068
Weight
Simultaneity between S1 and S2
Recovery time
Release time
Response time
Utilization category
Rated operational
voltage U
as per DIN VDE 0660
e
(V)
Part 200, IEC 60947-5-1
AC-15
230
DC-13
24
115
230
Continuous current I
th
Short-circuit protection Fuse links
for release circuit
Duty class
and signal circuit
Duty class
for enabling circuits
Please adhere to the respective user information!
and signaling circuits
(Order No.: C98130-A7524-A1-05-7419)
- Rated control supply voltage
The two-hand control unit is protected by an internal self-healing PTC fuse
(multifuse).
Be sure to fit the specified fuses. Otherwise safe interruption
in the event of a fault cannot be guaranteed.
For further data and accessories see Catalog.
C575
DIN EN / IEC 60947-5-1
English
Operation
not activated
only S1 activated
only S2 activated
S1 and S2 activated
–25 to +60 °C / –40 to +80 °C
300 V
4 kV
24 V DC, 24 V AC, 115 V AC, 230 V AC
3 W / 4 VA
0.85 to 1.1 x U
s
8 g / 10 ms
0.45 kg
< 0.5 s
minimum 250 ms
max. 20 ms
max. 100 ms
Rated operational current I
e
(A)
60 °C
70 °C
6
4
6
4
0.2
0.2
0.1
0.1
6
4
DIAZED
gL (gG) 6 A / quick response 10 A
gL (gG) 6 A / quick response 6 A
gL(gG) 2 A

Werbung

loading