10. Notes for mounting, ... / 11. Maintenance
10.3.2 Intrinsically safe supply and signal circuit
(4 ... 20 mA loop; terminal ⊕ und ⊖)
Parameters
GB
Terminals
Voltage U i
Strength of current I i 130 mA
Power P i
Effective internal
capacitance C i
Effective internal
inductance L i
*) The maximum operating current is limited by the T32. The maximum output current of the
associated energy-limited apparatus does not have to be ≤ 23 mA.
10.3.3 Connection of the HART
(terminal ⊕ and ⊖)
The sum of all voltages connected (supply plus output values of
the HART
exceed 30 V for T32.xx.0IS and 40 V for T32.xx.0NI.
The sum of the effective capacitances and inductances must not
exceed the maximum permissible value according to the required
equipment group (IIA up to IIC).

11. Maintenance

The temperature transmitter described in these operating instructions
is maintenance-free! The electronics are completely encapsulated
and incorporate no components which could be repaired or replaced.
Repairs must only be carried out by the manufacturer.
40
Model T32.xx.0IS
Gas hazardous
application
+ / -
DC 30 V
800 mW
7.8 nF
100 µH
The supply and signal circuit and the intrinsically safe
sensor circuit must be considered as galvanically
connected to each other.
modem and / or HART
®
WIKA operating instructions temperature transmitter T32.xS
Dust hazardous
application
+ / -
DC 30 V
130 mA
750/650/550 mW 1 W
7.8 nF
100 µH
modem/HART
®
Communicator) must not
®
Model T32.xx.0NI
Gas hazardous
application
+ / -
40 V
23 mA *)
7.8 nF
100 µH
communicator
®