Siemens RVP102/SET Installationsanleitung Seite 8

Heizungsregelung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Settings
1. Set heating curve slope as specified in the plan-
ning documentation or in compliance with local
practices, using setting knob
2. Based on the operating instructions, the following
settings must be made or checked on the room
unit:
-
Time of day and weekday
-
Heating program
-
Setpoints
-
Operating mode
Setting elements
3 4
Coding switches
Function
Base point of heating
curve
Frost protection, yes / no
Changeover of compen-
sating variable, yes / no
Pump overrun, yes / no
Setting potentiometers
The settings must be determined during the planning phase. If missing, the following guide values can be used.
Potentiometer
Function
Switching differential
of boiler temperature
control
Authority of room
temperature on boiler
temperature control
Heating limit for ECO
automatic
energy saver
8/16
31.01.2006
1
2
5
6
Switch position on the left
Base point at 20 °C flow
temperature
Yes, frost protection
No changeover; always
weather-compensated con-
trol and room temperature
authority according to set-
ting of potentiometer E
Six-minute pump overrun
Setting range
1...20 K
0...100 % authority
OFF = quick setback is
inactive
–10...+8 °C (referred
to the room tempera-
ture setpoint)
CE1G2466X
T
T
V35
V20
110
115
100
105
90
95
80
85
70
75
60
65
50
55
40
45
30
35
20
20
10
0
T
Flow temperature with a base point at 20 °C
V20
T
Flow temperature with a base point at 35 °C
V35
T
Outside temperature [°C]
A
1
Setting potentiometer for switching differential
2
Setting knob for heating curve slope
3
Coding switches
4
Setting potentiometer for authority of room temperature
and quick setback active / inactive
5
Setting potentiometer for ECO heating limit
6
Heating curve chart
Symbol
Symbol
Switch position on the right
Base point at 35 °C flow tem-
35°C
perature
No, no frost protection
Changeover to room tem-
perature-compensated control
at a reduced level
0 minutes, no pump overrun
0 Min.
Guide value
6 K
50 % (quick setback
is active)
–3 K (gives a heating
limit of 16 °C at a
room temperature
setpoint of 20 °C)
4 319 2719 0 d
Building Technologies / HVAC Products
3
2,5
2,25
4
3,5
2,75
2
1,75
1,5
1,25
1
0,75
0,5
0,25
-10
-20
-30
T
A
Notes