3.

Description

3.1

General function

CoolServe complies with the conditions of EN 60950
The slide-in design facilitates the installation to all 3 HU and 19" levels and slots.
Heat produced by installed equipment (e. g. servers) is reliably removed using the cold water
system integrated into the server cabinet. The cooling system is inherently safe because water
cannot reach the server area.
The cooling system comprises a high-performance air/water heat exchanger, fans with fan control
unit (fan-speed according to temperature) as well as a control valve for cooling performance
adjustment.
The air circuit is closed such that no heat (thermal load) is emitted to the environment.
Attention! CoolServe only works if cold server feed air
and heated server outlet air are fully separated.
Height units not in use have to be sealed using blanking panels.
Top view of a
rack with
CoolServe
CoolServe
01_998_345_0_a
page / Seite 7/77