Refuelling

The controller can signal a small amount of fuel re-
maining in the tank. In order for the calculation to be
possible, the current amount of fuel in the tank must
be set every time after adding fuel. You can set the
quantity using the "+" and "-" buttons or with the slider.
You can also start the fuel feeder on the screen at any
time; this may be necessary if the fuel is completely
used to fill the feed tube.
Date & Time
In order to set the date or time on the main screen,
press the date or time, respectively, which will result
in a window to set the date or time.

Schedule

The controller allows the boiler operation, heating
and DHW making up, in accordance with preset dai-
ly programmes for each day of the week separately.
Press the schedule button to enter the timer menu on
the boiler status, heating or DHW screens.
After clicking on the chart from a given day, you will
proceed to programming that day. In order to set the
required ranges, select the time and then choose,
which programme should be activated for the select-
ed time. You can set the program every hour.
PELLUX 100/20 TOUCH
PELLUX 100/30 TOUCH
The controller features convenient copying of the pro-
grammes to other days of the week. To do this, se-
lect the COPY button. After selecting this function, a
menu will appear with the days of the week, for which
you want to copy the selected programme. After se-
lecting the days, confirm with the "OK" button. After
returning to the programme for a given day, confirm
your selection with the "OK" button.

Boiler Operating Modes

You can adjust the boiler temperature set point and
operating mode by pressing the Operating modes
button on the main screen.
Symbol
Function
Boiler temperature is user defined. The
manual
boiler always operates to achieve pre-
defined temperature.
Boiler temperature is defined automat-
ically pursuant to current demand of
automatic
heating circuits, domestic hot water or
buffer.
Boiler temperature is defined as if in
time -
the manual mode, but the boiler can
manual
only operate in specific time intervals.
Boiler temperature is defined as if in the
time -
automatic mode, but them the boiler can
automatic
only operate in specific time intervals.

Factory settings

In order to restore factory settings:
1. In menu "Menu level (PIN)" enter the factory code.
Factory code
0023
0024
0025
0026
2. Turn off power supply for 10-15 seconds.
After restarting, driver should read factory settings
dedicated for the selected boiler. In "MENU/Software
info" we can check if the settings has been properly
loaded.
Section 5 |
First Start-Up & Operation of the Boiler
Opis
Boiler type
PELLUX COMPACT 12
PELLUX 100/20
PELLUX 100/30
PELLUX 200
EN
13