Frontplatte - ABB REA 101 Bedienhandbuch

Lichtbogenschutzrelais
Inhaltsverzeichnis

Werbung

1MRS756843 A
5.9.
Lichtbogenschutzrelais
Bedienhandbuch

Frontplatte

Uaux
Current
Light
TRIP
IRF
Sensor Fault
Optolink 1 Fault
Optolink 2 Fault
Port A Fault
Port B Fault
Reset
Trip Condition
Light
Current
SG1
1 2 3 4 5 6 7 8
SG1
xIn
0.5
1.0
1.5
2.5
3.0
5.0
6.0
S
1
ON
ON
OFF
OFF
OFF
OFF
OFF
2
OFF
OFF
ON
ON
OFF
OFF
OFF
3
OFF
OFF
OFF
ON
OFF
ON
OFF
4
OFF
ON
OFF
OFF
ON
ON
ON
5
AUTOMATIC LIGHT
REF. LEVEL ON/OFF
6
SENSOR ON/OFF
PORT A ON/OFF
7
PORT B ON/OFF
8
SG4
xIn
0.05
0.10
0.15
0.25
0.30
0.50
0.60
S
1
ON
ON
OFF OFF
OFF OFF OFF
2
OFF OFF ON
ON
OFF OFF
OFF
3
OFF OFF OFF ON
OFF ON
OFF
4
OFF ON
OFF OFF
ON
ON
ON
5
I
ON/OFF
0
Order
No: REA101-AAA
Serial
No: ES 135001
Abb. 5.9.-1 REA 101 Frontplatte
ARC PROTECTION
Light Ref.
Level Adj.
&
Light
Min
SG2
SG3
SG4
1 2 3 4 5 6 7 8
1 2 3 4 5
SG2
SG3
ON = INPUT
1
HSO2 IN USE
1
MODE
OFF = OUTPUT
OPTO-
2
I> START
SIGNAL
LINK 1
2
TRIP3 IN USE
3
LIGHT
TYPE
4
TRIP
ON = INPUT
3
DELAY
MODE
5
OFF = OUTPUT
OPTO-
6
I> START
SIGNAL
LINK 2
7
LIGHT
SENSOR SUPERVISION
4
TYPE
DEACTIVATION ON/OFF
8
TRIP
L2 current treshold setting note!
Current input 2 is used as neutral current I
SG4 switch 5 ON:
current treshold is selected with SG4 switches 1...4
SG4 switch 5 OFF:
All current inputs are used for phase currents,
current treshold is selected with SG1 switches 1...4
Uaux=110-240 Vac
Uaux=110-250 Vdc
fn
=50/60 Hz
REA 101
REA 101
Max
ON
OFF
1 2 3 4 5
CBFP
Note!
Can only be
used when trip
condition is
ON = 150ms
Current&Light
OFF = 100ms
input,
0
In=1/5 A
A050326
21