18
Installation
WARNING
2. Use two M3 screws to fix the magnetic sensor design L via the ø3.1 mm
through holes (fastening torque = 1 Nm).
Use two M2.5 screws to fix the magnetic sensor design B-TR via the two
threaded holes (fastening torque = 1 Nm).
Fig. 6: Definition of counting direction
<1°
Fig. 7: Assemblage sensor / magnetic tape, gap measure, tolerances

4.4 Electrical installation

Destruction of parts of equipment and loss of regulation control
` All lines for connecting the magnetic sensor must be shielded.
` Never wire or disconnect electrical connections while they are live.
` Perform wiring work in the de-energized state only.
` Use strands with suitable ferrules.
` Wiring to the screen and ground (0 V) must be secured to a good
point. Ensure that the connection of the screen and earth is made to a
large surface area with a sound connection to minimize impedance.
` Check all lines and plug connections before switching on the device.
` Switch on operating voltage together with the downstream electronic
unit (e. g., control unit).
MS100/1 · Date 27.04.2018 · Art. No. 82106 · Mod. status 118/18
1
2
<3°
English
Travel direction sensor,
counting direction negative
Direction of outgoing cable
Active side magnetic tape
1
Admissible deviation of
2
tape/sensor
≤0.4 mm
Maximum alignment error
3