LERBAKKEN 10, 8410 RØNDE DENMARK.
For safe installation of 5343B the following must be observed. The module shall only be Installed by
qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
Certificate
Marking
Standards
Hazardous area
Zone 0, 1, 2, 20, 21, 22, M1
T4: -40 ≤ Ta ≤ 85ºC
T5: -40 ≤ Ta ≤ 60ºC
T6: -40 ≤ Ta ≤ 45ºC
Terminal: 3,4,6
Uo: 30 VDC
Io: 8 mA
Po: 60 mW
Lo: 35 mH
Co: 66 nF
Revision date:
2013-06-03
IECEx Installation drawing
IECEx DEK 13.0036X
Ex ia IIC T4...T6 Ga
Ex ia IIIC Da
Ex ia I Ma
IEC 60079-0 : 2011, IEC 60079-11 : 2011, IEC 60079-26:2006
6
4
5343B
3
Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10 μH
Ci: 1.0 nF
Version Revision
V1R0
5343V107-DE
WWW.PRELECTRONICS.COM
Non Hazardous Area
+
1
-
2
Barrier
5343QI01