Herunterladen Inhalt Inhalt Diese Seite drucken

Dip Switches - ABB ACS55 Betriebsanleitung

Vorschau ausblenden Andere Handbücher für ACS55:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 46
14

DIP switches

DIP switches are used to adapt ACS55 to the motor and the application.
Warning! The DIP switch is at a dangerous voltage (200 V). Turn off power and wait for 5 minutes before adjusting the switches.
Keep the protective cover closed when ACS55 is powered.
Configuration
• Open the front cover using the tip of a screwdriver, and adjust the DIP switches.
• Use the tip of a screwdriver to slide the switch to the left or right. By default, all switches are in their left position.
• Close the front cover.
Basic information
DIP switch
#
Name and function
1
NOM FREQ HZ: Motor nominal frequency
2
SILENT: Motor noise level (PWM switching
frequency)
3
LOAD: Load torque type (U/f curve)
4
JOG HZ: Constant frequency for the jogging function 5 Hz
5
RELAY: Relay output operation
6
AI OFFSET: Minimum value for analogue input
7
AUTORESET: Automatic fault reset function
8
HI FREQ: High frequency mode
Default
Alternative
setting
setting
50 Hz
60 Hz
OFF - Normal
ON - Silent (16 kHz)
(5 kHz)
P&F - Pump/fan
CT - Constant torque
10 Hz
FLT - Fault
RUN - Motor running
OFF - 0 mA (0 V)
ON - 4 mA (2 V)
OFF - No autoreset
ON - Autoreset enabled
OFF - Standard
ON - High frequency
enabled
EN

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis