Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 69
18. ALARM CODES
If RUN lamp flashes for 2 seconds, there is a failure in
transmission between Indoor Unit and Remote Control
Switch. Possible causes are:
Remote Cable broken
Contact Failure in Remote Control Cable
IC or Microcomputer defective
In any case, ask your contractor for service
Code
Category
Content of Abnormality
No.
01
Indoor Unit
Tripping of Protection Device
02
Outdoor Unit
Tripping of Protection Device
Abnormality between Indoor (or Outdoor) and
03
Transmission
Outdoor (or Indoor)
04
Inverter
Abnormality between Inverter and Control PCB
04.
05
Transmission
Abnormality of Power Source Wiring
Voltage Drop by Excessively Low or High Voltage
06
Voltage Drop
to Outdoor Unit
07
Decrease in Discharge Gas Superheat
Cycle
08
Increase in Discharge Gas Temperature
09
Outdoor Unit
Tripping of Protection Device
11
Inlet Air Thermistor
12
Outlet Air Thermistor
Sensor on
13
Freeze Protection Thermistor
Indoor Unit
14
Gas Piping Thermistor
19
Tripping of Protection Device for Fan Motor
21
High Pressure Sensor
22
Outdoor Air Thermistor
23
Discharge Gas Thermistor on Comp.
24
Evaporating Thermistor
29
Low Pressure Sensor
30
Incorrect wiring connection
Sensor on
31
Incorrect Setting of Outdoor and Indoor Unit
Outdoor Unit
32
Abnormal Transmission of Other Indoor Unit
35
Incorrect Setting in Indoor Unit No.
36
Incorrect Indoor unit Type
38
Abnormality of Protective Circuit in Outdoor Unit
Abnormality of Running Current at Constant
39
Compressor
43
Pressure Ratio Decrease Protection Activating
44
Low Pressure Increase Protection Activating
Pressure
45
High Pressure Increase Protection Activating
46
High Pressure Decrease Protection Activating
47
Low Pressure Decrease Protection Activating
51
Abnormality of Current Sensor for Inverter
52
Overcurrent Protection Activating
53
Inverter
IPM Protection Activating
54
Increase in Inverter Fin Temperature
56
Abnormality of Detection for Fan Motor Position
57
Outdoor Fan
Fan Controller Protection Activating
58
Abnormality of Fan Controller
EE
Inverter
Compressor Protection
If RUN lamp flashes 5 times (5 seconds) with unit number and
alarm code displayed, note the alarm code (see table below)
and ask your contractor for service.
Unit Number
Alarm Code
Refrigerant Cycle Number
Number of connected Units
Leading Cause
Failure of Fan Motor, Drain Discharge, PCB, Relay.
Activation of PSH
Incorrect Wiring. Failure of PCB. Tripping of Fuse. Power Supply
OFF
Failure in Transmission between PCBs
Fan controller transmission failure
Reverse Phase Incorrect Wiring.
Voltage Drop of Power Supply. Incorrect Wiring or insufficient
Capacity of Power Supply Wiring.
Excessive Refrigerant Charge. Expansion Valve Open Lock.
Insufficient Refrigerant. Ref. Leakage, Clogging or Expansion Valve
Close Lock
Failure of Fan Motor.
Failure of Thermistor, Sensor, Connection.
Failure of Fan Motor
Failure of Thermistor, Sensor, Connection
Incorrect wiring connection between outdoor unit, CH unit and
indoor unit
Incorrect Setting of Capacity Code.
Failure of Power Supply, PCB in other Indoor Unit. Failure of other
Indoor Unit of the same Refrigerant Cycle
Existence of the same Indoor Unit No. in the same Refrigerant Cycle
Indoor Unit is not for R410A
Failure of Indoor Unit PCB. Incorrect wiring. Connection to PCB in
Indoor Unit.
Overcurrent, Blown Fuse of Failure of Current Sensor.
Failure of Compressor, Inverter
Overload to Indoor in Cooling. High Temperature of Outdoor Air In
Heating Expansion Valve Open Lock
Overload Operation. Excessive Refrigerant. Clogging of Heat
Exchanger
Insufficient Refrigerant.
Insufficient refrigerant .
Failure of Sensor on Inverter PCB
Overload, Overcurrent, Locking to Compressor.
Automatic Stoppage of IPM (Overcurrent, Low Voltage or
Overheating).
Abnormal Inverter Fin Thermistor.
Abnormal Outdoor Fan
Abnormal detection Circuit of Transmission
Abnormal Fan Speed
Overcurrent, Abnormal Fan Controller Fin
3 Time Occurrence of Alarm Giving Damage to Compressor within 6
hours
ALARM CODES
31
Model Code

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis