Tightening
FSN(E)
HP
Liquid
RAS-5FSN
16.5
RAS-8FSN(E)
16.5
RAS-10FSN(E)
16.5
RAS-16FSN
24.5
RAS-20FSN
30.0
RAS-24FSN
44.1
RAS-30FSN
44.1
FXN(E)
Liquid
Gas Valve
HP
Valve
RAS-8FXN(E)
16.5
RAS-10FXN(E)
16.5
RAS-16FXN
24.5
RAS-20FXN
30.0
RAS-24FXN
44.1
RAS-30FXN
44.1
Hexagonal Wrench Size (mm)
Model
Liquid Valve
RAS-5FSN
4
RAS-8FSN(E)
4
RAS-10FSN(E)
4
RAS-16FSN
4
RAS-20FSN
6
RAS-24FSN
10
RAS-30FSN
10
Liquid
Model
Gas Valve Low
Valve
RAS-8FXN(E)
RAS-10FXN(E)
4
RAS-16FXN
RAS-20FXN
RAS-24FXN
10
RAS-30FXN
(As for wrenches of 5mm and 10mm, use field-supplied
wrenches.)

14. DRAIN PIPING

Outdoor Unit Drain-Kit (DBS-26) (Optional
Accessory)
In the case that drain water from the heat exchanger of the
outdoor unit is required to be collected, use the Drain Kit.
However, it is not recommended to use it in a snow fall
area. If the drain water is required to be collected
completely, provide a field-supplied drain pan under the
outdoor unit.
Ø32
(N.m)
Gas
29.4
44.1
49.0
49.0
58.8
58.8
58.8
(N.m)
Gas Valve
Low
High
49.0
44.1
49.0
44.1
58.8
49.0
58.8
49.0
58.8
49.0
58.8
49.0
Gas Valve
8
10
10
10
10
10
10
Gas Valve
High
10
10
CAUTION:
Do not apply force to the spindle valve at the end of
opening (5.0 N.m or smaller). The back seat
construction is not provided.
During the test run, fully open the spindle. If it is not
fully opened, the devices will be damaged.
Caution on Refrigerant Leakage
Specifiers/installers have responsibility to follow local codes
and regulation which specify safety requirements against
refrigerant leakage
Maximum Permissible Concentration of HCFC/HFC Gas
The refrigerant R410A, charged in the SET-FREE FSN
system, is an incombustible and non-toxic gas. However, if
leakage occurs and gas fills a room, it may cause
suffocation.
The maximum permissible concentration of HCFC/HFC
gas, R410A in air is 0.44 kg/m³, according to EN378-1
Therefore, some effective measure must be taken to lower
the R410A concentration in air below 0.44 kg/m³, in case of
leakage.
Calculation of Refrigerant Concentration
1. Calculate the total quantity of refrigerant R (kg) charged
in the system connecting all the indoor units of rooms to
be air-conditioned.
2. Calculate the room Volume V (m³) of each room.
3. Calculate the refrigerant concentration C (kg/m³) of the
room according to the following equation:
R
R: Total Quantity of Charged Refrigerant (kg)
C
V: Room Volume (m³)
V
C: Refrigerant Concentration 0.44 kg/m³ for R410A
Countermesure for Refrigerant Leakage According to
KHK Standard
1. Provide a shutterless opening which allow fresh air to
circulate into the room.
2. Provide a doorless opening of 0.15% or more size to the
floor area.
3. Pay a special attention to the place, such as a
basement, etc., where refrigerant can stay, since
refrigerant is heavier than air.
Drain Kit
Model
Quantity (units)
RAS-5FSN
RAS-8/10/16FSN(E)
RAS-16FXN/20/24/30
DRAIN PIPING
19
3
4
8