UNITS INSTALLATION

12
11. UNITS INSTALLATION

11.1. INSTALLATION SPACE

Installation Place
-
Install the outdoor unit in a place where there is
adequate space around the unit for operating and
maintenance as shown below.
Front
Side
*Add the half of dimension H to 300mm for air intake space of rear side,
when the wall of rear side is higher than 500mm.
-
Install the outdoor unit where a good ventilation is
available.
-
Install the outdoor unit where it is in the shade or it will
not be exposed to direct sunshine or direct radiation
from high temperature heat source.
-
Install the outdoor unit where the falling ice from the
unit will not create a hazard, as in the case of
installation on top of a building where ice may fall
down on the pedestrians.
-
Install the outdoor unit where the sound or discharge
air from the outdoor unit does not affect neighbors or
environment.
-
Check to ensure that the foundation is flat and
sufficiently strong.
-
Do not install the outdoor unit where dust or other
contamination could block the outdoor heat
exchanger.
-
When installing the outdoor unit in snow-covered
areas, mount the field-supplied hoods on the top of
the outdoor unit and the inlet side of the heat
exchanger.
-
Do not install the outdoor unit where there are high-
levels of oil mist, salty air or aggressive gases such as
sulfur.
-
Do not install the outdoor unit where electromagnetic
waves are directly radiated to the electrical box and
inverter components.
-
Install the outdoor unit as far as practical at least 3
meters from the electromagnetic wave radiation, as
electronic noise can cause miss-operation of the unit.
NOTE:
In certain cases, a fuse may be blown and the system
my stop in high electro-magnetic turbulence
environment.
In certain cases, the system can get an alarm in high
electro-magnetic turbulence environment. In such
case, stop and start the system to clear the alarm.
CAUTION:
Aluminum fins have very sharp edges. Pay attention
to the fins to avoid any injury.
NOTE:
Install the outdoor unit on a roof or in an area where
people except service engineers can not touch the
outdoor unit.
Exemple of units installations if do you want more
information check the technical catalogue.
1. Basic Space
Rear Side Intake Space
300
500
Front Side Intake Space
(Top View)
*A space of 900mm is recommended for easier service work.
2. Multiple Installation Space
Min. 300
Min.
Min. 20
10
600 to 900
Front Side
*
The maximun Outdoor Unit quantity should be in A in one block.
A: 5 to 16FSN(E)
3 units
8 to 10FXN(E)
3 units
20 to 30FSN
2 units.
16 to 30FXN
2 units.
(mm)
Air Intake
Side View
Min. 10