Electronic overload relays for potentially explosive areas
EF19 ... EF750
EF65
EF45
EF19
EF205
EF146
General description
The extended risks when using the devices in potentially explosive areas require the consistent adherence to the following notes
and standards:
EN 60079-7 Explosive atmospheres – Part 7: Equipment protection by increased safety "e"
EN 60079-14 Explosive atmospheres - Part 14: Electrical installations design, selection and erection
EN 60079-17 Explosive atmospheres - Part 17: Electrical installations inspection and maintenance
EN 50495 Safety devices required for the safe functioning of equipment with respect to explosion risks
The electronic overload relays of the EF series are authorized under device group II, category (2) in the "G" area (areas with
potentially explosive gas, steam, smoke or air mixtures) and additionally for the "D" area (areas with combustible dust).
BVS 15 ATEX F 001
II (2) G [Ex eb Gb] [Ex db Gb] [Ex pxb Gb]
II (2) D [Ex tb Db] [Ex pxb Db]
Explanations
Explosive gas atmospheres according to EC 60079
[Ex eb]
Increased safety
[Ex db]
Flameproof enclosure
[Ex pxb]
Pressurized enclosure
Combustible dust according to IEC 61241
[Ex tb]
Protection by enclosure
[Ex pb]
Pressurized enclosure
The EF electronic overload relays are not suitable for erection and/or operation in potentially explosive areas. When using the
devices in potentially explosive areas, they must comply to the required type of protection by corresponding measures.
For starter combinations with EF overload relays and AF motor contactors, as well as for DBxxEF single installations, an
appropriate protection against short-circuit is to be selected for reaching coordination type "2" according to EN 60947-4-1.
Respective information regarding verified starter combinations are provided online by ABB.
see "Coordination tables for motor protection"
http://applications.it.abb.com/SOC/Page/Selection.aspx
2CDC107043M6801g / 09 .2017
EF96
EF370
EF460
EF750
Warning! Hazardous voltage!
Safety instructions
Mounting and installation may only be done by
trained technical personnel, according to the
recognized technical rules, regulations, and
relevant standards!
Insufficiently tightened locking screws lead to
an inadmissible rise in temperature!
Always observe the permitted ambient
conditions (see technical data and catalog).
Devices with a visible transport damage must
not be used.
IECEx BVS 17.0016
[Ex]
|
ATEX EF19 ... EF750 - 7