2.3 Installation of the air pressure switch and
the alarm sensor
Before installing the sensor clean and grease the
seating gasket. Insert the air pressure switch into
position (see illustration 5) and secure with the red
hand securing clasp. Place the optical probe /
alarm in position f (see illustration 5) in the appro-
priate opening. Prior to doing this the purple ope-
ning plug must be removed.

2.5 Installation example

➀ KESSEL qualift F Compact Wastewater Lifting Station
➁ Control unit with SDS (Self Diagnosis System)
➂ Outlet pressure pipe should be increase to at least size DN 70 immediately
after the outlet pipe's loop above the backwater level
➃ Ventilation to roof
➄ Inlet
➅ Connection to ventilated drainage pipe
2. Installation

2.4 Noise protection

For noise reduction the pump base as well as the
pressure outlet should be properly installed as to
prevent vibration transfer. Use the included anti
vibration matt under the Aqualift F Compact (see
illustration 5)
In case the area of installation poses a flood risk,
the Aqualift F Compact should be secured to the
floor to prevent floatation. This can be done with
the included securing brackets.
25
Art. 28743
Art. 28040
ill. 6