Dell PowerApp 100 Rack-Installationsanleitung Seite 15

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

support.dell.com
  
1.
Determine where you want to place the bottom of the system.
        !      #      
     $      
2.
Place the 1-U template over the front of the two-posts of the rack in the desired
location.
3.
Position the bottom of the template in line with the desired bottom position of
the system chassis.
4.
Mark the upper and lower-mounting positions on the vertical rails as shown by
the V-notches on the sides of the template.
Each 1-U (1.75-inch) vertical space has three holes, with center-to-center spacing
between holes (beginning at the center of the top hole of a 1-U space) of 0.625,
0.625, and 0.5 inch (see Figure 1-5).
1.75 inches (1 U)
 %      !
0.5 inch
0.625 inch
0.625 inch
0.5 inch
Rack Installation Guide
1-7