Chauvin Arnoux C.A 6549 Bedienungsanleitung Seite 87

Megohmmeter
Vorschau ausblenden Andere Handbücher für C.A 6549:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

ST
ND
PI (m/m): 1
et 2
times for the PI calculation.
Set Step Function 1, 2, 3: for each predefi ned step function, defi nition of the various voltages, of
the duration of each step, and of the interval for the recording of samples. To skip a step, set the
duration or the voltage to "---".
Step Function 1
Step 1
Step 2
Step 3
Step 4
Step 5
Step Function 2
Step 1
Step 2
Step 3
Step 4
Step 5
Step Function 3
Step 1
Step 2
Step 3
Step 4
Step 5
Note: the minimum sample time depends on the total duration of the test (Total Run Time). It is equal to
Sample Time (seconds) = (h+1)*5 where h= hours of the Total Run Time.
Default value
01 / 10 (m/m)
Default value
Voltage
Duration (h:m)
50 V
00: 01
100 V
00: 01
150 V
00: 01
200 V
00: 01
250 V
00: 01
sample time
00: 10 (m:s)
100 V
00: 01
300 V
00: 01
500 V
00: 01
700 V
00: 01
900 V
00: 01
sample time
00: 10 (m:s)
1000 V
00: 01
2000 V
00: 01
3000 V
00: 01
4000 V
00: 01
5000 V
00: 01
sample time
00: 10 (m:s)
87
Range
0.5 ... 30
(0.5-, then 1-min steps)
/1 ... 90
(0.5-, then 1-, then 5-min steps)
Range
Voltage
Duration (h:m)
40 ... 5100 V
00: 09 ... 09: 59
i n 1 0 - V t h e n
100-V steps
00: 09 ... 09: 59
00: 09 ... 09: 59
00: 09 ... 09: 59
00: 09 ... 09: 59
see note
(00: 05...59: 59)
The limit depends
on the duration set
for the Timed Run.
40 ... 5100 V
i n 1 0 - V t h e n
00: 09 ... 09: 59
100-V steps
00: 09 ... 09: 59
00: 09 ... 09: 59
00: 09 ... 09: 59
00: 09 ... 09: 59
see note
(00: 05...59: 59)
The limit depends
on the duration set
for the Timed Run.
40 ... 5100 V
00: 09 ... 09: 59
i n 1 0 - V t h e n
100-V steps
00: 09 ... 09: 59
00: 09 ... 09: 59
00: 09 ... 09: 59
00: 09 ... 09: 59
see note
(00: 05...59: 59)
The limit depends
on the duration set
for the Timed Run.