Troubleshooting

5
Troubleshooting
Use only original spare parts. Damage caused by the use of spare parts
not supplied by the manufacturer are excluded from the warranty.
▶ If a fault cannot be rectified, please contact your local service
engineer.
The indicator at the coding switch shows the operating condition of the
module. Additional status indicators are:
[1]
Alternative heat source
[2]
Bypass valve/heating circuit pump
[3]
Accumulator tank
[4]
Block of conventional heat source
1
4 5 6
3
2
1
0
5.1

Indicator of module

Operating Icon
Possible cause
Constantly OFF
Power supply
interrupted.
Fuse is defective
Short circuit in the
BUS connection
Constantly red
Temperature sensor
briefly incorrectly
connected.
Coding card in invalid
position or in
intermediate
position.
Only with stand-
alone alternative
heat source: outside
temperature sensor
faulty
Internal fault.
Flashing yellow
Initialisation
Constantly green Coding card set to 0. ▶ Set the coding card.
No fault
Table 12
32
2 3 4
7
8
9
10
0010014042-001
Remedy
▶ Turn on the mains power supply.
▶ When the power supply is
switched off, replace the fuse
( Fig. 17 at end of this
document).
▶ Check BUS connection and
repair if required.
▶ Turn the module off and back on.
▶ Set the coding card.
▶ Check temperature sensor.
▶ If values do not match, replace
the sensor.
▶ Check voltage at temperature
sensor terminals in the module.
▶ If the sensor values match but
the voltage values do not,
replace the module.
▶ Replace module.
Normal operation
5.2

Indicator of alternative heat source

Status indicator Possible cause
Constantly OFF
no heat requirement Normal operation
Constantly red
Temperature sensor
briefly incorrectly
connected.
Flow/return
temperature sensor
of alternative heat
source defective
Solid yellow
Heat requirement or
flue gas temperature
≥ 100 °C (with stove)
Constantly green No fault
Table 13
5.3

Indicator of bypass valve/heating circuit pump

Status indicator Storyline Protocol
Constantly OFF
Stand-alone alternative heat source
Pump of heating circuit 1 off; no heat requirement and no
heat flow through heating circuit 1
System with conventional heat source
Bypass valve open; conventional heat source blocked and
hydraulically bypassed
Constantly green Stand-alone alternative heat source
Pump for heating circuit 1 on
System with conventional heat source
Bypass valve closed, conventional heat source released and
hydraulically connected
Table 14
5.4

Buffer cylinder indicator

Status indicator Possible cause
Constantly OFF
Temperature sensor
not available
Constantly red
Temperature sensor
briefly incorrectly
connected.
Faulty buffer cylinder
temperature sensor
or heating system
flow/return
temperature sensor.
Solid yellow
Buffer cylinder is at
least 10 K below the
set temperature
Constantly green Buffer cylinder is at
the most 5 K below
the set temperature
Table 15
AM200 – 6720871012 (2017/06)
Remedy
▶ Turn the module off and back on.
▶ Check temperature sensor.
▶ If values do not match, replace
the sensor
▶ Check voltage at temperature
sensor terminals in the module.
▶ If the sensor values match but
the voltage values do not match,
replace the module
Normal operation or heat-up phase
(transitional phase to normal
operation)
Normal operation
Remedy
▶ Check connection of
temperature sensor.
▶ Check temperature sensor.
▶ Check connection of
temperature sensor.
▶ Turn the module off and back on.
▶ Check temperature sensor.
▶ If values do not match, replace
the sensor.
▶ Check voltage at temperature
sensor terminals in the module.
▶ If the sensor values match but
the voltage values do not match,
replace the module
Normal operation